Step
|
Action
|
Result
|
---|---|---|
1
|
To launch OS Loader, click Start → Programs → EcoStruxure Control Expert → OS Loader.
|
The Welcome window is displayed.
|
2
|
Keep the default settings of the context file and proceed to the next step by clicking Next....
|
The Communication Protocol window is displayed.
|
3
|
Select the FTP communication driver.
Proceed to the next step by clicking Next....
|
The FTP Target window is displayed.
|
4
|
Select Direct Device, enter the IP address in the FTP Address field (see preconditions) and click Connect.
Remark: If requested, enter the MAC address of the target PLC. The MAC address can be found on the front of the module.
|
|
5
|
Click Next >.
|
The Operation window is displayed.
|
6
|
Select Download OS to device, click Browse... and select the file.
|
|
7
|
Proceed to the next step by clicking Next....
Green markers must be present. If not, the selected file and device are incompatible. The filename and device name must be identical.
|
The File and Device Info window is displayed.
|
8
|
Proceed to the next step by clicking Next....
|
The Summary window is displayed.
|
9
|
Click Download.
|
The Progress - Initialization window is displayed meaning that the operating system is downloaded to the processor.
|
10
|
When the download is completed, the Progress (100%) window appears, click Close in the different windows to exit OSLoader.
|
|
11
|
The device needs at least 60 seconds to reboot and implement the new Exec files. When this process is completed, the RUN and STS LEDs on the module are lit for at least 30 seconds.
Remark: If the RUN and STS LEDs do not lit steady during 30 seconds after 2 minutes, perform a power cycle on the module.
Check the new OS version.
|
|
12
|
Repeat the procedure as many times as needed to transfer the various files.
|