Step
|
Action
|
Result
|
---|---|---|
1
|
To launch OS Loader, click Start → Programs → EcoStruxure Control Expert → OS Loader.
|
The Welcome window is displayed.
|
2
|
Keep the default settings of the context file and proceed to the next step by clicking Next....
|
The Communication Protocol window is displayed.
|
3
|
Select the driver to be used for communication between the PC and the PLC.
Proceed to the next step by clicking Next....
|
The protocol window is displayed.
|
4
|
As Device Type:
Remark 1: for the Local Head, the Slot Number indicates the position of the target module in the rack.
Remark 2: for the Remote I/O Drop, the Slot Number indicates the position of the target module in the rack and the Drop Number indicates the remote target module address.
|
|
5
|
For a Premium processor, click Connect.
For a Quantum processor or other target device:
For an Ethernet port:
|
In the Device area the active node Node: SYS-PLC is displayed (Premium).
|
6
|
Select the active node Node: SYS-PLC.
Remark: If the PLC is not already stopped, Stop PLC button can be used, this action is password protected on Safety PLCs, otherwise, the PLC will be stopped at step 11. Make sure no other Control Expert is connected to the PLC.
Proceed to the next step by clicking Next....
|
The Operation window is displayed.
|
7
|
Select Download OS to device, click Browse... and select the file.
|
|
8
|
Proceed to the next step by clicking Next....
|
A message is displayed.
|
9
|
Click OK.
Green markers must be present. If not, the selected file and device are incompatible. The filename and device name must be identical.
|
The File and Device Info window is displayed.
|
10
|
Proceed to the next step by clicking Next....
|
The Summary window is displayed.
|
11
|
Click Download.
Remark: If the PLC is not already stopped, you are asked to do so, this action is password protected on Safety PLCs. Make sure no other Control Expert is connected to the PLC.
|
A message is displayed.
|
12
|
Click Yes.
|
The Progress - Initialization window is displayed meaning that the final operating system is downloaded to the processor.
|
13
|
When the download is completed, the Progress (100%) window appears, click Close in the different windows to exit OSLoader.
|