Overview
The Topology Manager is the user interface that opens when you start Control Expert with the appropriate license. It lets you engineer control systems that contain several PACs and provides additional functionality.
Control Expert Editor is the name given to Control Expert Classic that opens inside the Topology Manager when you edit the control project of a . Certain configuration parameters and commands are now unavailable in the editor. You need to configure the corresponding attributes and use the corresponding commands in the Topology Manager instead.
General Actions
The table indicates in which tool you need to perform a given action.
Action |
Topology Manager |
Control Expert Editor |
---|---|---|
Configuration - Offline |
||
Creating PACs and controllers with their associated control project - all platforms |
Yes |
|
Configuring M580 CPU modules (replace, configuration other than communication, such as I/O objects). |
Yes |
|
All actions on modules (add, move, replace, delete, and configuration other than communication). |
Yes |
|
All actions on a rack (add, move, replace, delete) |
Yes |
|
Configuration - Online |
||
All actions |
Yes |
|
Programs |
||
All actions |
Yes |
|
Animation Tables |
||
All actions |
Yes |
|
Operator Screens |
||
All actions |
Yes |
|
Documentation |
||
All actions |
Yes |
|
Data |
||
Derived data types |
Yes |
|
Derived FB types |
Yes |
|
Variables and FB instances |
Yes |
|
Ethernet Networks (M580 platform) |
||
Creating and managing networks, assigning IP addresses |
Yes |
|
Communication Networks (platforms other than M580) |
||
Creation, assigning IP addresses |
Yes |
I/O Devices and Master Modules
The table indicates in which tool you need to create and configure I/O devices and configure master modules of Modicon M580 PACs.
Action |
Topology Manager |
Control Expert Editor |
---|---|---|
EtherNet/IP/Modbus TCP I/O Devices |
||
Creating devices |
Yes |
|
Network configuration of devices |
Yes |
|
Configuring parameters of DTMs |
Yes (inside the DTM) |
|
Creating DTMs from EDS and GSD files |
Yes |
|
Updating the local DTM catalog |
Yes |
|
Master Module Network Configuration |
||
M580 CPU |
Yes |
|
Communication modules (Other than those listed below) |
Yes |
|
BMECRA31310 |
Yes |
Yes (some I/O scanning parameters, time stamping buffer) |
BMECXM0100 |
Yes (IP and DHCP configuration) |
Yes (security, services, Ethernet I/O, CANopen configuration) |
BMENOP0300 |
Yes |
Yes (by using the IEC 61850 configuration Tool) |
BMENOR0200 |
Yes (I/O objects) |
|
BMENOR2200 |
Yes |
Yes (communication channels and services) |
BMENOS0300 |
Yes |
|
BMENUA0100 |
Yes |
Yes (time stamping for version .2) |
BMXNGD0100 BMXNOC0402 BMXNOM0200 BMXEIA0100 |
Yes |
|
HART analog input/output modules |
Yes (network and fieldbus) |
Yes (analog module) |
PROFIBUS remote master (PRM) |
Yes |
|
BMXPRA0100 (Additional actions to be performed in Control Expert Classic) |
Yes |
|
PMEPXM0100 |
Yes (IP configuration, services, I/O profile, and DTM) |
Yes (by using the ProSoft Configurator for Modicon Tool) |
Implicit Messaging (I/O scanning) |
||
Communication and I/O mapping |
Yes |
|
Local slaves |
Yes |
The table indicates in which tool you need to configure communication parameters of Modicon M340 and MC80 PACs, and Quantum, Premium, and Momentum controllers.
Action |
Topology Manager |
Control Expert Editor |
---|---|---|
Ethernet Devices Network Configuration |
||
Communication module network configuration |
Yes |
|
I/O scanning |
Yes |
Downloads to Controllers or Devices and Uploads From Controllers
The table indicates in which tool you need to perform a given action.
Action |
Topology Manager |
Control Expert Editor |
---|---|---|
Download to Controllers or Devices |
||
Transferring the full project to controllers |
Yes (to one or more M580 PACs) |
Yes (to single controller only(1)) |
Transferring project changes to controllers |
Yes (to single controller only(1)) |
|
Downloading the configuration to one or more I/O devices |
Yes |
|
Upload From Controllers |
||
Uploading application from M580 PACs. |
No (only supported in Control Expert Classic) |
|
Uploading application from controllers other than M580 platform |
Yes |
No |