Overview
This topic describes how to set up communication between a BMXPRA0100 module and an M580 PAC acting as master in a system project.
The procedure requires using both Control Expert Classic and the Topology Manager.
The BMXPRA0100 module is represented in the system project by a generic Modbus TCP device, which is scanned by the M580 PAC.
Creating the BMXPRA0100 Control Project With Control Expert Classic
Step |
Action |
---|---|
1 |
Open Control Expert Classic. |
2 |
Create a new control project of the Modicon M340 platform and select the BMXPRA0100 module. NOTE: You can
also open an existing control project in .sta or .zef file format, which contains a BMXPRA0100 module. In such case, proceed to step
4.
|
3 |
Configure the modules and create the logic that will be exchanged with the M580 PAC. |
4 |
Save the project to disk as project file (.stu). |
5 |
Close Control Expert Classic. |
Configuring Communication in the Topology Manager
Step |
Action |
---|---|
1 |
Open the system project. |
2 |
In the BMXPRA0100 module. node of the pane, create a generic , which represents the |
3 |
Attach the control project file (.stu) containing the BMXPRA0100 to the device. |
4 |
Configure the I/O profile of the device and create the item mapping according to the data to be exchanged with the M580 PAC. |
5 |
Create and configure the M580 PAC. |
6 |
Open the Modbus TCP Communication Mapping View from the M580 CPU module. |
7 |
Add the I/O profile of the device to a scanner of the PAC. |
8 |
Complete the engineering life cycle of the system project. |