The J block is used for analog outputs, with individual fusing provided per channel. This interface provides plus, minus, shield, and power supply interfaces for both field and loop power configurations.
The following figure shows the 140CFJ00400 terminal block.
The following are the application notes for the 140CFJ00400 module.
-
Configuration – Four analog outputs with a common loop supply. Each point is allocated six terminals.
-
Compatibility – This terminal block provides four individually 0.063 A fused connection point sets for the 140ACO02000 analog output module.
The following figures show the dimensions for the 140CFJ00400 module.
Wiring Diagram (Source Grounding)
The following figure shows the wiring for the 140CFJ00400 (source grounding) module.
NOTE:
-
When using a single power supply, there will be no channel-to-channel isolation of input points.
-
-
The GND (ground) terminal point is not connected.
Wiring Diagram (Instrument Grounding)
The following figure shows the wiring for the140CFJ00400 (instrument grounding) module.
NOTE:
-
When using a single power supply, there will be no channel-to-channel isolation of input points.
-
-
The GND (ground) terminal point is not connected.
Wiring Diagram (Chassis Grounding)
The following figure shows the wiring for the 140CFJ00400 (chassis grounding) module.
NOTE:
-
When using a single power supply, there will be no channel-to-channel isolation of input points.
-
-
The GND (ground) terminal point is not connected.