Step
|
Action
|
---|---|
1
|
Double-click the DTM for the BMENOC0301 in slot 3 (<192.168.20.10> BMENOC0301_slot3) to access the configuration.
NOTE: This example uses a BMENOC0301 module. Use the same instructions for other M580 communications modules (like the BMENOC0311 or BMENOC0321). |
2
|
In the navigation tree, expand the Device List to see the associated local slave instances.
|
3
|
Select the device that corresponds to the name NIC2212_01 to see the Properties and Address Setting tabs.
|
Field
|
Parameter
|
Description
|
---|---|---|
Properties
|
Number
|
Accept the auto-generated value.
|
Active Configuration
|
Accept the default (Enabled).
|
|
IO Structure Name
|
Structure Name
|
Control Expert automatically assigns a structure name based on the variable name, in this case T_STBNIC2212_from_EDS.
|
Variable Name
|
Variable Name: Accept the auto-generated variable name (based on the alias name): STBNIC2212_from_EDS.
|
|
Default Name
|
Press this button to restore the default variable (T_NIC2212_01) and structure (NIC2212_01) names. For this example, custom names are used.
|
|
Items Management
|
Import Mode
|
Select Manual.
|
Reimport Items
|
Press this button to import the I/O items list from the device DTM, overwriting any manual I/O item edits. Enabled only when Import mode is set to Manual.
|
Field
|
Parameter
|
Description
|
---|---|---|
Change Address
|
IP Address
|
Enter the IP address 192.168.1.6.
|
Address Server
|
DHCP for this Device
|
Select Enabled.
|
Identified by
|
Select Device Name.
|
|
Identifier
|
Accept the default setting (based on the Alias name).
|
|
Mask
|
Accept the default value (255.255.255.0).
|
|
Gateway
|
Accept the default value (0.0.0.0).
|