Step
|
Action
|
---|---|
1
|
In the DTM Browser (Tools → DTM Browser), double-click the DTM that corresponds to the Ethernet communication module.
|
2
|
In the navigation pane, expand (+) the Device List to see the associated Modbus TCP and EtherNet/IP devices.
|
3
|
Select a device from the Device List to view the Properties, Address Setting, and Request Setting tabs.
NOTE: These tabs are described in detail below. |
Field
|
Parameter
|
Description
|
---|---|---|
Properties
|
Number
|
The relative position of the device in the list.
|
Active Configuration
|
Enabled: Add this device to the Control Expert project configuration.
|
|
Disabled: Remove this device from the Control Expert project configuration.
|
||
IO Structure Name
|
Structure Name
|
Control Expert automatically assigns a structure name based on the variable name.
|
Variable Name
|
Variable Name: An auto-generated variable name is based on the alias name.
|
|
Default Name
|
Press this button to restore the default variable and structure names.
|
|
Items Management
|
Import Mode
|
Manual: I/O items are manually added in the Device Editor. The I/O items list is not affected by changes to the device DTM.
|
Automatic: I/O items are taken from the device DTM and updated if the items list in the device DTM changes. Items cannot be edited in the Device Editor.
|
||
Reimport Items
|
Press this button to import the I/O items list from the device DTM, overwriting any manual I/O item edits. Enabled only when Import mode is set to Manual.
|
Field
|
Parameter
|
Description
|
---|---|---|
Change Address
|
IP Address
|
By default:
In our continuing example, type in the address 192.168.1.17.
|
Address Server
|
DHCP for this Device
|
Enabled: Activate the DHCP client in this device. The device obtains its IP address from the DHCP service provided by the Ethernet communication module and appears on the auto-generated DHCP client list.
|
Disabled (default): Deactivates the DHCP client in this device.
|
||
NOTE: For this example, select Enabled. |
||
Identified by
|
If DHCP for this Device is Enabled, it indicates the device identifier type:
NOTE: For this example, select Device Name. |
|
Identifier
|
If DHCP for this Device is Enabled, the specific device MAC Address or Name value.
NOTE: For this example, accept the default setting of NIP2212_01 (based on the Alias name). |
|
Subnet Mask
|
The device subnet mask.
NOTE: For this example, accept the default value (255.255.255.0). |
|
Gateway
|
The gateway address used to reach this device. The default of 0.0.0.0 indicates this device is located on the same subnet as the Ethernet communication module.
|
Step
|
Action
|
---|---|
1
|
Press the Add Request button to see a new request in the table.
Press the Add Request button:
NOTE: The Add Request function is enabled only when Import Mode on the Properties tab is set to Manual. |
2
|
Configure the request settings according to the table below.
|
3
|
Repeat these steps to create additional requests.
|
4
|
Press the Apply to save the request.
|
Setting
|
Description
|
---|---|
Connection Bit
|
This bit indicates the read-only offset for the health bit for this connection. Offset values (starting at 0) are auto-generated by the Control Expert DTM based on the connection type.
|
Unit ID
|
The Unit ID is the number used to identify the target of the connection.
NOTE: Consult the manufacturer’s user manual for the specific target device to find its Unit ID. |
Health Time Out (ms)
|
This value represents the maximum allowed interval between device responses before a time out is detected:
|
Repetitive Rate (ms)
|
This value represents the data scan rate in intervals of 5 ms. (The valid range is 0...60000 ms. The default is 60 ms.)
|
RD Address
|
Data that is read from the remote device at this address is stored in the input data image of the Ethernet communication module.
|
RD Length
|
This value represents the number of words (0...125) in the Modbus device that the communication module reads.
|
Last Value
|
This value represents the behavior of input data in the application if communications are lost:
|
WR Address
|
The output data image in the Ethernet communication module's data structure is written to this address in the remote Modbus device.
|
WR Length
|
This value represents the number of words (0...120) in the Modbus device to which the communication module writes.
|
Gateway/Bridge Device
|
This feature lets slower TCP/IP network devices (i.e., gateways and bridges) communicate with the I/O Scanner:
|
Step
|
Action
|
---|---|
1
|
Click a row in the table.
|
2
|
Press the Remove button to remove the request.
NOTE: The corresponding request items disappear from the Device List. |
3
|
Press the Apply to save the configuration.
|