Step
|
Action
|
---|---|
1
|
Launch Control Expert Configuration screen.
|
2
|
Replace the CPU from V1.0, V2.0, V2.1, V2.2, V2.3, or V2.4 to V2.5 (or later).
NOTE: CANopen CPUs higher than V2.0 are provided with a new part number. |
3
|
Build the application and transfer it to the CPU.
|
Step
|
Action
|
---|---|
1
|
Launch Control Expert Configuration screen.
|
2
|
Delete the BMX NOE 01•0 module.
|
3
|
Replace the CPU from V1.0, V2.0, V2.1, V2.2, V2.3, or V2.4 to V2.5 (or later).
|
4
|
Add the BMX NOE 01•0.2 module.
|
5
|
Change the Ethernet network Model Family from NOE 0100, NOE 0110 to NOE 0100.2, NOE 0110.2 (in Project Browser → Communication → Networks select the concerned Ethernet network).
|
6
|
Enable (set to Yes) the following network parameters if they were previously configured:
|
7
|
Link this family to the BMX NOE 01•0.2 module.
|
8
|
Build the application and transfer it to the CPU.
|