Word (dec)
|
Control Expert-IEC bits
|
Quantum Function
|
System Word
|
||
|---|---|---|---|---|---|
|
1
|
Controller Status:
|
–
|
|||
|
0...3
|
Not used, always 0
|
||||
|
4
|
1 = battery non-operational
|
||||
|
5
|
Always 1 = memory protect OFF
|
||||
|
6
|
1 = RUN light OFF
|
||||
|
7
|
1 = AC power on
|
||||
|
8
|
16b/24b User Logic
|
||||
|
9
|
1 = enable single sweep delay
|
||||
|
10
|
1 = enable constant sweep
|
||||
|
11...15
|
Not used, always 0
|
||||
|
2
|
Hot standby Status:
|
%SW61
|
|||
|
0 and 1
|
local system state:
|
||||
|
Bit 1
|
Bit 0
|
State
|
|||
|
0
|
1
|
Off line (1 dec)
|
|||
|
1
|
0
|
primary (2 dec)
|
|||
|
1
|
1
|
standby (3 dec)
|
|||
|
2 and 3
|
remote system state:
|
||||
|
Bit 3
|
Bit 2
|
State
|
|||
|
0
|
1
|
Off line (1 dec)
|
|||
|
1
|
0
|
primary (2 dec)
|
|||
|
1
|
1
|
standby (3 dec)
|
|||
|
4
|
application mismatch
|
||||
|
5
|
unit A or B
|
||||
|
6
|
CPU-sync link status
|
||||
|
7
|
all firmware (CPU, copro, CRP) mismatch
|
||||
|
8
|
copro firmware mismatch
|
||||
|
9...11
|
Not used, always 0
|
||||
|
12
|
Info validity
|
||||
|
13
|
IP or IP+1
|
||||
|
14
|
Not used, always 0
|
||||
|
15
|
set to 1, if hot standby mode
|
||||
|
3
|
Controller status (more aspects):
|
–
|
|||
|
0...3
|
single sweeps
|
||||
|
4...11
|
Not used, always 0
|
||||
|
12
|
1 = existing DIM AWARENESS
|
||||
|
13
|
1 = constant sweep time exceeded
|
||||
|
14
|
1 = start command pending
|
||||
|
15
|
1 = first scan
|
||||
|
4
|
Not used, always 0
|
–
|
|||
|
5
|
Controller stop state:
|
–
|
|||
|
0
|
1 = bad config
|
||||
|
1
|
not used in RUN mode
|
||||
|
2
|
Logic checksum
|
||||
|
3
|
Invalid Node
|
||||
|
4
|
Not used, always 0
|
||||
|
5
|
CPU logic solver cannot solve
|
||||
|
6
|
1 = real time clock detected error
|
||||
|
7
|
1 = watchdog timer expired
|
||||
|
8
|
Bad number of I/O module on I/O bus or End of Logic Nodes
|
||||
|
9
|
1 = state RAM test detected fault
|
||||
|
10
|
Start of Node did not start Segment
|
||||
|
11
|
Segment Scheduler Invalid
|
||||
|
12
|
1 = "SoftError" (HALT)
|
||||
|
13
|
1 = controller in DIM AWARENESS
|
||||
|
14
|
error detected in the I/O mapping
|
||||
|
15
|
1 = peripheral port stop
|
||||
|
6
|
Not used, always 0
|
–
|
|||
|
7
|
Not used, always 0
|
–
|
|||
|
8
|
4 = RIO redundancy and timeout
|
–
|
|||
|
9
|
Not used, always 0
|
–
|
|||
|
10
|
Not used, always 0
|
–
|
|||
|
11
|
Not used, always 0
|
–
|
|||
|
Word (dec)
|
Control Expert-IEC bits
|
Quantum Function
|
System Word
|
|---|---|---|---|
|
12
|
I/O module health status for drop 1 (Standalone or Primary PLC main rack):
|
%SW180
|
|
|
0
|
slot 16
|
||
|
...
|
...
|
||
|
15
|
slot 1
|
||
|
13
|
I/O module health status for drop 1 (Standalone or Primary PLC extension rack).
|
%SW181
|
|
|
14
|
I/O module health status for drop 1 (Standby PLC main rack).
|
%SW182
|
|
|
15
|
I/O module health status for drop 1 (Standby PLC extension rack).
|
%SW183
|
|
|
16
|
Not used, always 0
|
%SW184
|
|
|
17
|
I/O module health status for drop 2 rack 1 (main rack).
|
%SW185
|
|
|
18
|
I/O module health status for drop 2 rack 2 (extension rack).
|
%SW186
|
|
|
...
|
...
|
...
|
|
|
167
|
I/O module health status for drop 32 rack 1 (main rack).
|
%SW335
|
|
|
168
|
I/O module health status for drop 32 rack 2 (extension rack).
|
%SW336
|
|
|
169
|
I/O module health status for drop 32 rack 3 (extension rack).
|
%SW337
|
|
|
170
|
I/O module health status for drop 32 rack 4 (extension rack).
|
%SW338
|
|
|
171
|
I/O module health status for drop 32 rack 5 (extension rack).
|
%SW339
|
|
|
Word (dec)
|
Control Expert-IEC bits
|
Quantum Function
|
System Word
|
|---|---|---|---|
|
172
|
S908 startup detected error code: This word is always 0 when the system is running. If an error is detected, the controller does not start, it generates a stop state code of 10 (word 5).
|
%SW535
|
|
|
173
|
Cable A detected error:
|
%SW536
|
|
|
0...7
|
counts DMA receiver overruns
|
||
|
8...15
|
counts detected framing errors
|
||
|
174
|
Cable A detected error:
|
%SW537
|
|
|
0...7
|
counts bad drop receptions
|
||
|
8...15
|
counts detected receiver errors
|
||
|
175
|
Cable A detected error:
|
%SW538
|
|
|
0
|
Not used, always 0
|
||
|
1
|
1 =overrun error detected
|
||
|
2
|
1 = alignment error detected
|
||
|
3
|
1 = CRC error detected
|
||
|
4...13
|
Not used, always 0
|
||
|
14
|
1 = no end-of- frame
|
||
|
15
|
1 = short frame
|
||
|
176
|
Cable B detected error:
|
%SW539
|
|
|
0...7
|
counts DMA receiver overruns
|
||
|
8...15
|
counts detected framing errors
|
||
|
177
|
Cable B detected error:
|
%SW540
|
|
|
0...7
|
counts bad drop receptions
|
||
|
8...15
|
counts detected receiver errors
|
||
|
178
|
Cable B detected error:
|
%SW541
|
|
|
0
|
Not used, always 0
|
||
|
1
|
1 =overrun error detected
|
||
|
2
|
1 = alignment error detected
|
||
|
3
|
1 = CRC error detected
|
||
|
4...13
|
Not used, always 0
|
||
|
14
|
1 = no end-of- frame
|
||
|
15
|
1 = short frame
|
||
|
179
|
Global communication status:
|
%SW542
|
|
|
0...7
|
cumulative retry counter
|
||
|
8...11
|
lost communication counter
|
||
|
12
|
Not used, always 0
|
||
|
13
|
1 = cable B status
|
||
|
14
|
1 = cable A status
|
||
|
15
|
1 = comm health
|
||
|
180
|
Global cumulative detected error counter for Cable A
|
%SW543
|
|
|
181
|
Global cumulative detected error counter for Cable B
|
%SW544
|
|
|
Word (dec)
|
Control Expert-IEC bits
|
Quantum Function
|
System Word
|
|---|---|---|---|
|
182
|
First word: Local drop status
|
%SW545
|
|
|
0...7
|
number of times a module has been seen as unhealthy; counter rolls over at 255
|
||
|
8...14
|
Not used, always 0
|
||
|
15
|
1 = all modules healthy
|
||
|
183
|
Second word: This word is a 16-bit detected error counter, which indicates the number of times a module has been accessed and found to be unhealthy.
Rolls over at 65535.
|
%SW546
|
|
|
184
|
Third word: This word is a 16-bit detected error counter, which indicates the number of times a communication error was detected while accessing an I/O module.
Rolls over at 65535.
|
%SW547
|
|
|
Word (dec)
|
Control Expert-IEC bits
|
Quantum Function
|
System Word
|
|---|---|---|---|
|
185
|
First word: Communication status for the appropriate drop 2.
|
%SW548
|
|
|
0...7
|
cumulative retry counter
|
||
|
8...11
|
lost communication counter
|
||
|
12
|
Not used, always 0
|
||
|
13
|
1 = cable B status
|
||
|
14
|
1 = cable A status
|
||
|
15
|
1 = communication health
|
||
|
186
|
Second word: the drop cumulative detected error counter on cable A for the drop 2.
|
%SW549
|
|
|
187
|
Third word: the drop cumulative detected error counter on cable B for the drop 2.
|
%SW550
|
|
|
188...190
|
Drop 3 errors/health status and retry counters: First, second, and third words.
|
%SW551
...
%SW553
|
|
|
...
|
...
|
...
|
|
|
275...277
|
Drop 32 errors/health status and retry counters: First, second, and third words.
|
%SW638
...
%SW640
|
|