S908 Detected Error Codes
(Original Document)
Detected Error Codes
The table below provides the S908 detected error codes on startup:
Code
Detected Error
Meaning (Where the error has occurred)
01
BADTCLEN
traffic cop length
02
BADLNKNUM
remote I/O link number
03
BADNUMDPS
number of drops in traffic cop
04
BADTCSUM
traffic cop checksum
10
BADDDLEN
drop descriptor length
11
BADDRPNUM
I/O drop number
12
BADHUPTIM
drop holdup time
13
BADASCNUM
ASCII port number
14
BADNUMODS
number of modules in drop
15
PRECONDRP
drop already configured
16
PRECONPRT
port already configured
17
TOOMNYOUT
more than 1024 output points
18
TOOMNYINS
more than 1024 input points
20
BADSLTNUM
module slot address
21
BADRCKNUM
module rack address
22
BADOUTBC
number of output bytes
23
BADINBC
number of input bytes
25
BADRF1MAP
first reference number
26
BADRF2MAP
second reference number
27
NOBYTES
no input or output bytes
28
BADDISMAP
discrete not on 16-bit boundary
30
BADODDOUT
unpaired odd output module
31
BADODDIN
unpaired odd input module
32
BADODDREF
unmatched odd module reference
33
BAD3X1XRF
%I reference after %IW word
34
BADDMYMOD
dummy module reference already used
35
NOT3XDMY
%IW module not a dummy
36
NOT4XDMY
%MW module not a dummy