Remote Drop Considerations
Original instructions
Introduction
The guidelines in this topic refer to these remote drops:
Racks and Extensions
A remote drop that includes a 140CRA31908 module can have two racks (main rack and extended rack). These racks are linked with a 140XBE10000 bus extender module and a 140•CA7170• cable (1-3m).
Maximum Configuration
A Quantum remote drop with a 140CRA31908 module can include two 16-slot racks for a maximum of 32 slots. The table shows the maximum number of modules:
Module Type
Number of Modules
Note
140CRA31908
1
A 140CRA31908 module consumes one slot in the main remote rack of a Quantum remote drop. The extended remote rack does not require a 140CRA31908 module.
power supply
2
A power supply consumes one dedicated slot in each rack.
bus extension
2
A bus extender module is required for each rack. The bus extender consumes one rack slot.
I/O
27
Supported CPUs
These M580 CPU modules are compatible with the 140CRA31908 module:
CPU
Supports ...
X80 Remote Drops
Quantum S908 Remote Drops
BMEP584040
DIO, X80 remote drops
16
31
BMEP585040
DIO, X80 remote drops
31
31
BMEP586040
DIO, X80 remote drops
31
31
BMEH584040
DIO, X80 remote drops, redundant networks
16
31
BMEH586040
DIO, X80 remote drops, redundant networks
31
31
Supported Adapter Modules
These X80 adapter modules are compatible with the 140CRA31908 module and can be used on the same Ethernet main ring:
Product Range
Module
Quantum
140CRA31200
Modicon X80
BMXCRA31200
BMXCRA31210
BMECRA31210
Supported RIO Modules
M580 architectures support the drop-end communication modules in the following tables.
Quantum range support:
Adapter Module
RIO Cable Ports
140CRA93100
1
140CRA93200
2
Control Expert does not support the ACSII read (READ) and write (WRIT) functions for ACSII. Therefore, the ACSII ports on the P453, P892, and J892 modules are no longer accessible. You can manage ACSII communications as follows:
800 Series I/O range support:
Module
ASCII Ports
RIO Cable Ports
3220
0
1
3240
0
1
410
0
1
J890/P8••
0
1 or 2
J892/P8••
2
1 or 2
P890-••1
0
1
P890-••2
0
2
P890 300
2
2
P892-••1
2
1
P892-••2
2
1
SY/MAX range support:
Module
Type
8030CRM931DG2
RIO adapter module
8030CRM931DG4
8030CRM931DG8
8030CRM931DG1
8030CRM931RG
register RIO adapter module
Supported S908 I/O Modules
M580 architectures support S908 I/O modules in the following tables.
Quantum range support:
I/O Module
Reference
discrete
all
generic I/O (see note)
analog
all (including intrinsically safe 140AI•33•••)
generic analog I/O (see note)
communication
140EIA92100 AS-i, 140NRP95400/140NRP95401C fiber optic repeater, 140XBE10000 extender
expert
all (140ERT85410/20 time stamp, 140DCF07700 clock, 140ESI06210 serial line ASCII, two-port RS232C [12 registers bidirectional], 140XCP90000 battery)
motion
single-axis motion (MSX) modules, 140MSB10100 incremental encoder, resolver/encoder
power supply
all
800 Series range support (discrete modules):
I/O Module
Type
Range
Channels
Comment
B802-008
out
80...130 Vac cont.
8
individually isolated
47...63 Hz
B803-008
in
80...130 Vac cont.
8
individually isolated
47...63 Hz
B804-116
out
80...130 Vac cont.
16
isolated
47...63 Hz
2 groups, 8 points/group
B804-148
out
40...56 Vac
16
isolated
47...63 Hz
2 groups, 8 points/group
B805-016
in
80...130 Vac cont.
16
isolated
47...63 Hz
2 groups, 8 points/group
B806-032
out
80...130 Vac cont.
32
47...63 Hz
B806-124
out
20...28 Vac cont.
32
2 groups, 16 points/group
47...63 Hz
32 Vac RMS max. for 10 sec
B807-132
in
80...130 Vac cont.
32
4 groups, 8 points/group
47...63 Hz
B808-016
out
80...260 Vac cont.
16
2 groups, 8 points/group
47...63 Hz
B809-016
in
160...260 Vac cont.
16
2 groups, 8 points/group
47...63 Hz
B810-008
out
80...130 Vac cont.
8
isolated
47...63 Hz
B814-108
out
0...30 Vdc
8
relay
0...240 Vac
47...63 Hz
B817-116
in
115 Vac
16
isolated
B817-216
in
230 Vac
16
isolated
B820-008
out
10…60 Vdc
8
true high
B821-108
in
10…60 Vdc
8
true high
B824-016
out
20…28 Vdc
16
true high
B825-016
in
20…28 Vdc
16
true high
B827-032
in
18…30 Vdc
32
true high
B828-016
out
5 V TTL
16
B829-116
in
5 V TTL
16
high-speed TTL
B832-016
out
20…28 Vdc
16
true low
B833-016
in
20…28 Vdc
16
true low
B836-016
out
12…250 Vdc
isolated
B837-016
in
20.3...27 Vac
16
isolated
47...63 Hz
2 groups, 8 points/group
19.2…30 Vdc
B838-032
out
20…30 Vdc
32
true high
B840-108
out
0...300 Vdc
16
relay
0...230 Vac max.
19.2…30 Vdc
B846-001
in
0...5 V
16
1 word out (BIN)
1...5 V
+/- 10 V
B846-002
in
4...20 mA
16
1 word out (BIN)
B849-016
in
41...53 Vac
16
true high
47...63 Hz
85...150 Vdc
B853-016
in
80...130 Vac
16
true high
47...63 Hz
85...150 Vdc
B855-016
in
11.4...12.6 Vdc
16
isolated
B863-032
in
18...30 Vdc true high
32
24 Vdc nominal
B863-132
in
0...30 Vdc
32
B864-001
out
8
8-channel reg. mux
B865-001
in
5 V TTL
8
8-channel reg. mux
B881-001
out
20…28 Vdc
16
B881-508
out
5...140 Vdc max.
8
B882-032
out
19.2...28 Vdc
32
B882-116
out
19.2...30 Vdc
16
800 Series range support (analog modules):
I/O Module
Type
Range
Channels
Comment
B846-001
IN
0...5 V
16
Reed-Relay-Multiplexer for voltage input as front end for B873/875 A/D converter
1...5 V
+/- 10 V
1 word (BIN)
B846-002
in
4...20 mA
16
Reed-Relay-Multiplexer for current input (250 ohm impedance) as front end for B873/875 A/D converter
1 word (BIN)
B872-100
out
4...20 mA
4
user supply required
B872-200
out
0...5 Vdc
4
operating range selectable per channel
0...10 Vdc
no user supply required
+/- 5 Vdc
+/- 10 Vdc
B873-002
in
1...5 Vdc
4
4 words (BIN)
4...20 mA
B875-002
in
1...5 Vdc
8
8 words (BIN)
4...20 mA
B873-012
in
+/- 10 Vdc
4
4 words out (BIN)
B875-012
in
+/- 10 Vdc
8
8 words out (BIN)
B875-102
in
1...5 Vdc
4 (8)
high speed
0...5 Vdc
0...10 V
+/- 5 V
+/- 10 V
4...20 mA
0...20 mA
0...40 mA
+/- 20 mA
+/- 40 mA
B875-111
in
1...5 Vdc
8 differential, 16 single
8 words (BIN) as B877 = 16 words (BIN)
0...5 Vdc
0...10 V
+/- 5 V
+/- 10 V
4...20 mA
0...20 mA
+/- 20 mA
B875-114
in
0...2 mA
8 differential
B875-200
in
4...20 mA
8
A/D converter with pluggable input amplifier modules
1...5 V
0...10 V
RTD/TC
0...10 V
0...20 mA
800 Series range support (special purpose modules):
I/O Module
Type
Range
Channels
Comment
B882-239
high-speed counter
30 kHz
4 inputs
350 Hz
3 outputs
B883-001
high-speed counter
50 kHz
2
3 outputs
B883-101
CAM
4
8
24 Vdc out
B883-200
thermocouple in
centigrade
10 in
open circuit detection
fahrenheit
self-calibration
millivolts
B883-201
RTD in
centigrade
8
Europe
fahrenheit
America
linear
B884-002
PID loop
n/a
2
open/closed loop
B885-002
ASCII/BASIC
n/a
2
RS2322
2
B885100/110
motion control
Communications between the CPU and the module are through the Traffic cop registers (3000x and 4000x, like a generic analog I/O module).
B984100
reflex
8 out, 16 in
contains the LL984 program and is running in standalone (exchanges 6 register bi-directional)
NOTE: Specific software packages may be required to complete the setting, programming, and monitoring for some of these modules (B884-002, B885-002, B885-100/110, B984-100).
SY/MAX range support:
Module
Type
8030RIM101
input modules
8030RIM121
8030RIM123
8030RIM125
8030RIM126
8030RIM127
8030RIM301
8030RIM331
8030RIM361
8030RIM731
8030ROM121
output modules
8030ROM122
8030ROM221
8030ROM421
8030ROM431
8030ROM441
8030ROM141
multiplex output module
8030RIM144
multiplex input module
8030ROM271
relay output modules
8030ROM871
8030RIM131
high-speed counter module
8030ROM131
stepper motor controller module
8030SIM116
simulator input module
Quantum CAPP Partner Modules
The following tables show supported modules that are produced by members of Schneider Electric's Collaborative Automation Partner Program (CAPP).
AVG partner (CAPP communication modules):
Module Type
Function
Personality Code
Comment
DeviceNet scanner (obsolete)
140SACQDNET010
313 (8/8 words), 320 (32/32 words)
Configure in Control Expert as a generic analog I/O module.
Niobrara Research & Development partner (CAPP communication modules):
Module Type
Function
Personality Code
Comment
universal communication module (protocol conversion, serial and Ethernet ports)
140QUCMOE, 140QUCMLE, 140QUCMSE
295 (30 input words, 30 output words)
Configure in Control Expert as a generic analog I/O module.
QASI AS-i master V3.0
QASI
356 (27 input words, 27 output words)
Configure in Control Expert as a generic analog I/O module. Can also be configured as an emulation of the 140EIA921 Quantum Asi adapter.
QSPXM Seriplex master (obsolete)
QSPXM
303
Configure as generic analog I/O module with 32 input registers (3x) and 32 output registers (4x), or as an I/O module with 512 discrete inputs (1x) and 512 discrete outputs (0x).
Spectrum Controls partner (CAPP input and output modules):
Module Type
Function
Personality Code
Comment
16 configurable analog input channels (RTD, thermocouple, current, or voltage)
140AUI04000
1060 (20 configuration registers max).
Configure in Control Expert as a generic analog I/O module mapped on 32 input registers (3x) and 32 output registers (4x).
Monaghan Engineering partner (CAPP modules):
Module Type
Function
Personality Code
Comment
GPS receiver
140GPS10000
307
Configure in Control Expert as a generic analog I/O module.
NB: Add MEI library from Monaghan to the Control Expert environment to get the GPS function block.
sequence event recording
140SER85300
302
Configure in Control Expert as a generic discrete I/O module mapped as 64 input bits (1x) and 64 output bits (0x), or as four input words (3x) and 4 output bits (4x).
AMCI partner (CAPP modules):
Module Type
Function
Personality Code
Comment
convert resolver signals to digital position
AMCI 1831Q 6I/10O
323
6 input bytes, 10 output bytes
AMCI 1832Q 12I/10O
323
12 input bytes, 10 output bytes
AMCI 1833Q 18I/10O
324
18 input bytes, 10 output bytes
AMCI 1834Q 24I/10O
324
24 input bytes, 10 output bytes
AMCI 1841Q 6I/10O
323
6 input bytes, 10 output bytes
AMCI 1842Q 12I/10O
323
12 input bytes, 10 output bytes
AMCI 1843Q 18I/10O
324
18 input bytes, 10 output bytes
AMCI 1844Q 24I/10O
324
24 input bytes, 10 output bytes
AMCI 1861Q 8I/20O
326
8 input bytes, 20 output bytes
AMCI 1862Q 16I/20O
326
16 input bytes, 20 output bytes