Installing the Adapter Module
Original instructions
Locate a Backplane Slot
Install the 140CRA31908 adapter module in any slot in the Quantum remote drop.
Refer to the directions for installing a module on the backplane.
Power Consumption
Power consumption is 1.2 A on a 5 Vdc power rail on the backplane (6 W). The 140CRA31908 module supports other Quantum modules on two racks (main rack and extended rack). (Power consumption has no relation to the number of installed rack modules.)
Select a Power Supply
When configuring the local rack, use a power supply module that can supply power to all rack modules.
Select a power module that suits your unique system requirements. These modules (and their conformally coated versions) are supported:
Power Supply Type
Quantum Module
standalone
140CPS2100 (C)
140CPS51100 (C)
140CPS11100 (C)
summable
140CPS21400 (C)
140CPS41400 (C)
140CPS11420 (C)
redundant
140CPS22400 (C)
140CPS42400 (C)
140CPS52400 (C)
140CPS12420 (C)