Description
Automatic
start in RUN is a processor configuration option. This option forces
the PLC to start in RUN after a cold restart, except after an application has
been loaded onto the PLC.
For Quantum PLCs, automatic start
in RUN also depends on the position of the switch on the front panel
of the processor. For more details, refer to the Quantum documentation.
WARNING |
---|
| UNEXPECTED SYSTEM BEHAVIOR - UNEXPECTED PROCESS START The following actions will trigger "automatic start in
RUN":
- Inserting the PCMCIA card when the PLC is powered up (Premium,
Quantum),
- Replacing the processor while powered up (Premium, Quantum),
- Unintentional or careless use of the reset button,
- If the battery is found to be defective in the event of a power
outage (Premium, Quantum).
To avoid an unwanted restart when in RUN mode:
- We stongly recommend to use the RUN/STOP input on Premium PLCs
or the switch on the front of the panel of the processor for Quantum
PLCs
- We strongly recommend not to use memorized inputs as RUN/STOP
input of the PLC.
Failure to follow these instructions can result in death, serious injury, or equipment damage. |