Main Ring Diagnostics
Original instructions
Diagnosing the Remote I/O Main Ring
You can monitor breaks in the remote I/O main ring by diagnosing the REDUNDANCY_STATUS bits in the 140CRP31200 remote I/O head module DDT. The system detects and reports in this bit a main ring cable break that persists for at least 5 seconds.
Within the REDUNDANCY_STATUS bit:
In a Hot Standby system, perform a BITWISE OR operation of the REDUNDANCY_STATUS bit in the DDTs for both the primary and standby 140CRP31200 modules to determine whether a cable break has occurred. As indicated above, a value of 0 indicates a cable break; a value of 1 indicates no cable break.
NOTE: Refer to the Quantum EIO Remote I/O Modules Installation and Configuration Guide for a list of diagnostic status bits.