Step
|
Action
|
---|---|
1
|
Upgrade the CPU (only with a 140 CPU 652 •• CPU or 140 CPU 672 •• CPU).
|
2
|
Add new modules or replace existing modules.
|
3
|
Change the application.
|
Step
|
Action
|
---|---|
1
|
Add the 140CRP31200 module to an empty slot in the local rack. With a Hot Standby configuration, add the 140CRP31200 module to both local racks.
|
2
|
Install the Ethernet remote I/O drops. Refer to the Module Selection topic for a list of compatible modules.
|
3
|
Add a 140NOC78000 distributed I/O head module (interlinked with the 140CRP31200 module) if you plan to add distributed I/O devices or diagnose the PLC remotely.
|
Step
|
Action
|
---|---|
1
|
Replace the 140CRP93•00 module with the 140CRP31200 module in the local rack. With a Hot Standby configuration, replace the 140CRP93•00 module with the 140CRP31200 module in both local racks.
|
2
|
Replace the 140 CRA 93• 00 adapter module with the 140CRA31200 adapter module in all Ethernet remote I/O drops.
|
3
|
Add a 140NOC78000 module (interlinked with the 140CRP31200 module) if you plan to add distributed I/O devices or diagnose the PLC remotely.
|
Step
|
Action
|
---|---|
1
|
Install Unity Pro V7.0 on the computer.
|
2
|
Check that the application program running in the Quantum CPU has been exported in the XEF format and is available on the computer. If not, upload the application program from the PLC and export it in the XEF format.
|
3
|
In Control Expert, import the XEF file of the application.
|
4
|
In the local drop editor, replace the actual processor version with the new version, V3.10.
|
5
|
Configure the new modules in the Control Expert application.
|
6
|
Depending on the type of upgrade (Case 1 or Case 2), modify the application program in order to manage the new Ethernet remote I/O drops (see below for the impacts of this modification).
|
7
|
Rebuild the application program and download it to the CPU. The CPU is in STOP mode. With a Hot Standby configuration, download the application in both PLCs.
|
8
|
Put the PLC in RUN mode.
|
Legacy (S908) Remote I/O
Diagnostic System Bits and words
|
Ethernet Remote I/O
Diagnostic System Bits and Words
|
---|---|
%S118: general detected fault
|
%S117: general detected fault
|
No equivalent available.
|
%SW152 to %SW153: drop status bits for remote I/O drops 1 to 31
|
No equivalent available.
|
%SW172 to %SW173: connection status bits for remote I/O drops 1 to 31
|
%SW185 to %SW339: module health bits for drop 1 to 31
|
%SW641 to %SW702: module health bits for remote I/O drops 1 to 31
|
%SW535: detected error on start up
|
No equivalent available.
|
%SW536 to %SW541: communication status (counters) on cable A and B
|
Communication status and counters can be read by using 140 CRP 312 00 head module and 140 CRA 312 00 adapter module DDT. For details, refer to the EcoStruxure™ Control Expert Program Languages and Structure Reference Manual.
|
%SW542 to %SW544: global communication status (counters)
|