Comparing Legacy (S908) Remote I/O Drops with Ethernet Remote I/O Drops
Original instructions
Introduction
In a Quantum EIO configuration, you can use both Ethernet remote I/O drops and legacy (S908) remote I/O drops. However, in order to benefit from Ethernet capabilities offered by a Quantum EIO system, you can migrate the legacy (S908) remote I/O system to Ethernet.
Comparing Legacy (S908) Remote I/O and Ethernet Remote I/O
The table below provides a comparison of the legacy (S908) remote I/O modules with the Ethernet remote I/O modules, focusing on their commonality – they are both Quantum remote I/O modules.
Legacy (S908) Remote I/O
Ethernet Remote I/O
local head module
140CRP93•00
140CRP31200
local head module configuration
Control Expert configuration on the local rack without parameters
Control Expert configuration on the local rack with network parameters
connectivity network protocol
proprietary
remote I/O modules
  • 800 series I/O
  • Quantum remote I/O
  • SY/MAX
Quantum remote I/O
Quantum remote I/O drops
drop configuration
parameters for module status data
parameters for module status data
racks
  • 140 XBP 002 00
  • 140 XBP 003 00
  • 140 XBP 004 00
  • 140 XBP 006 00
  • 140 XBP 010 00
  • 140 XBP 016 00
  • 140 XBP 002 00
  • 140 XBP 003 00
  • 140 XBP 004 00
  • 140 XBP 006 00
  • 140 XBP 010 00
  • 140 XBP 016 00
drop adapter module
140CRP93•00
•••CRA31200
drop adapter module configuration
Control Expert configuration on the remote rack without parameters
Control Expert configuration on the remote rack with network parameters
drop module types
  • supply
  • discrete
  • analog
  • counting
  • communication (XBE)
  • expert (ERT and ESI)
  • supply
  • discrete
  • analog
  • counting
  • communication (XBE)
  • expert (ERT and ESI)
module I/O mapping
bit address (flat addressing)
bit address (flat addressing)
improving response time
using section scheduler
using IU_EIO function block
remote I/O in project file
STU + STA + PLC (ETS) + XEF
STU + STA + PLC (ETS) + XEF + ZEF
diagnostic
bus diagnostic (drop, rack, module) based on %SW180-%SW339
bus diagnostic (drop, rack, module) based on %SW152-%SW153 (drops), %SW172-%SW173 (drops), and %SW641-%SW702 (modules) and using explicit messaging
CCOTF
Available with Unity Pro 5.0 or later
Available with Unity Pro 6.0 or later
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.
NOTE:
  • Ethernet remote I/O drops can support more I/O modules than a legacy (S908) remote I/O drop:
    • A legacy (S908) remote I/O drop is limited to 64 input words and 64 output words.
    • An Ethernet remote I/O drop is limited to 800 input bytes (400 input words) and 800 output bytes (400 output words).
  • When you replace legacy (S908) remote I/O drops with Ethernet remote I/O drops, if the global number of remote I/O modules is the same, you may reduce the number of Ethernet remote I/O drops to optimize network performance.