Electrical characteristics
|
Value
|
Unit
|
---|---|---|
Nominal voltage
|
24
|
V
|
Voltage limits
Temporary voltage
|
19 to 30
34 (1)
|
V
V
|
Nominal current
|
500
|
mA
|
Max voltage fall "On"
|
< 1
|
V
|
Leakage current at "OFF" state
|
< 0,3
|
mA
|
Load impedance
|
80<Zon<1500
|
Ω
|
Max current to 30 V and to 34 V
|
625
|
mA
|
Communication time
|
< 250
|
μs
|
Electro unload time
|
< L/R
|
s
|
Max switching frequency
(on inductive load)
|
F<0.6 / (LI2)
|
Hz
|
Compatibility with inductive inputs
|
Any input whose Re is less than 15 kΩ and has positive logic
|
|
IEC 1131 compatibility
|
Yes
|
|
Protection from overloads and short-circuits
|
by current limiter and circuit breaker
|
|
Monitoring short-circuits of each channel
|
thermal, signaling: 1 bit per channel
|
|
Reset
|
One bit per module
|
|
Protection against channel overvoltage
|
Zener (55 V) between outputs and +24 V
|
|
Protection against polarity inversions
|
Using a reverse diode on the supply
|
|
Power of a filament lamp
|
8
|
W
|
Pre-actuator voltage check
|
OK if supply > 18 (ascending)
not OK if supply < 14 (decreasing)
|
V
V
|
Reaction time of voltage check
|
NOK --> OK<30
OK --> NOK>1
|
ms
ms
|