Introduction

An X80 RIO drop can have one or two racks:

  1. main RIO rack: BMEXBP••00 or BMXXBP••0

    This rack is required in a drop and contains a BMXCRA31200, BMECRA31210, or BMXCRA31210 EIO adapter module, a power supply, and, optionally, I/O modules.

  2. extended RIO rack: only BMXXBP••0

    This rack is optional in a drop and contains only I/O modules.

    Confirm that extended remote racks are PV 02 or later. Install modules that require Ethernet across the backplane on the main remote rack.

    NOTE: The BMXCRA31200 does not support an extended RIO rack.
NOTE: The mounting screws on the left side of the backplane may be accessible without unplugging the power supply module. Mount the backplane using the far left fastening hole on the panel.

Compatible Racks

Use these racks in an Modicon X80 RIO drops:

  • X BUS (PV 02 or later) backplanes:

    • BMXXBP0400

    • BMXXBP0600

    • BMXXBP0800

    • BMXXBP1200

    • BMXXBP0400H

    • BMXXBP0600H

    • BMXXBP0800H

    • BMXXBP1200H

  • Ethernet backplanes:

    • BMEXBP0400

    • BMEXBP0602

    • BMEXBP0800

    • BMEXBP1002(2)

    • BMEXBP1200(1)

    • BMEXBP0400H

    • BMEXBP0602H

    • BMEXBP0800H

    • BMEXBP1002(2)

    • BMEXBP1200H(1)

(1) The 12-slot Ethernet rack has eight Ethernet-X Bus slots and four X Bus-only slots.

(2) The 10-slot Ethernet rack has eight Ethernet-X Bus slots and two X Bus-only slots.

Rack Selection Considerations

A BMECRA31210 performance EIO adapter module:

  • can be installed on an Ethernet rack only.

  • can be installed on a PV 02 or later backplane, but it cannot manage Ethernet modules.

  • cannot be installed in a PV 01 backplane because of its keying pin

A BMXCRA31210 or a BMXCRA31200 EIO adapter module:

  • can be installed on a PV 02 or later backplane.

  • can be installed on an Ethernet backplane, but it cannot manage Ethernet modules. However, it can manage modules that it manages on a PV 02 or later backplane.

Racks and Extensions

An Modicon X80 RIO drop can include two racks. In a 2-rack drop, the racks are linked with two bus extender modules and a cable:

Bus Extender Module

Cable

BMXXBE1000

BMXXBC•••K (0.8 to 12 m)

Consideration of a Shielded Cable with an Accessible Metal Part

Follow all local and national safety codes and standards.

Do not apply power to an Modicon X80 rack until connections are made at both ends of the Ethernet cable. For example, connect the cable to both the BMECRA31210 performance EIO adapter module and another device (adapter module) or DRS before you turn on the power.

Refer to your system hardware reference manual for details about DRSs.