Transferring M580 Hot Standby Projects
Original instructions
Introduction
In an M580 Hot Standby system, both the primary CPU and the standby CPU begin by operating the same application. CCOTF changes that are made to the application running in the primary CPU are not also made to the standby CPU. This causes a logic mismatch to exist between the two CPUs.
After modifications, it is necessary to transfer the application from the primary CPU to the standby CPU, so that both CPUs are once again operating the same application. There are many ways to make this transfer.
NOTE: The operating mode setting of a safety PAC – either safety mode or maintenance mode – is not included in the transfer of an application from the primary PAC to the standby PAC. On a switchover, when a safety PAC switches from standby PAC to primary PAC, the operating mode is automatically set to safety mode.
For additional information on safety CPU operating modes, refer to the Modicon M580 Safety Manual.
Transferring the Application from the Primary CPU to the Standby CPU
The Control Expert application can be transferred from the primary CPU to the standby CPU in many ways, including the following:
In each case:
NOTE:
  • You cannot transfer the application from the standby CPU to the primary CPU.
  • If the Logic_Mismatch_Allowed command is set, and if the Number of modifications has not been reached, you can connect Control Expert to the standby CPU, then use the CMD_SWAP DDT command to make the standby CPU the primary CPU. Thereafter, you can transfer the application from new primary CPU (formerly the standby) to the standby CPU (formerly the primary).
Run After Transfer
If you use program logic or an animation table to set the T_M_ECPU_HSBY DDT command CMD_RUN_AFTER_TRANSFER, the primary PAC automatically begins to run immediately upon completion of the transfer.