P890 and P892 Installation
(Original Document)
Introduction
The following procedure describes how to install a P890 or P892 processor. The processor is installed in an H819/H827-209 800 series I/O Housing in the left-most slot.
NOTE: To ensure proper operation of this module, you must have one of the following revisions (or higher) of Traffic Cop software:
P190 AS-T984-302 Version 2.01 Rev.J
IBM AS-DIBM-902 Version 3.01 Rev.X
If you do not have a tape or diskette with one of the above software levels, call Customer Service and obtain the proper software.
Procedure for Installation
How to Install a P890 or P892 processor
Step
Action
1
Set the address/handshake switch as shown in P890/P892 Drop Address Switch Settings.
2
Ensure that the power supply switches are OFF and power to the housing is OFF. Also, set the 115/230 VAC switch based upon your power requirement. Do not insert the P890 or P892 processor if power is supplied to the unit.
3
Remove the plastic cover to connect the power cables, once they are in place replace the plastic cover.
4
Wire up the power cable for either AC (three pin plug) or DC (two pin plug) depending upon the application.
5
Connect remote I/O cable to the P890 or P892 F-connector.
6
Remove the ASCII port connector covers. Connect the ASCII device cable(s). For the P892 only.
7
Insert the P890/P892 into the H819/H827-209 housing in the left-most slot. Press firmly to ensure that the processor is seated properly in the housing.
8
Tighten the two captive screws located at the top and bottom of the processor.
9