P890 and P892 Specifications
(Original Document)
Topology
Topology
Cabling
Single coaxial cable 75 ohm RG-6 type
Connector
F-Type
Communications
Communications
Rate
1.544 MHZ
Drop scan time
< 5 ms for 256 I/O points
Comm link time
< 1 ms for 256 I/O points
Drop hold up time
programmable from 300msec to 6553.6sec (100 msec increments)
Power Supplied to I/O
Power supplied to I/O
+5 VIO
@3 Amp*
+4.3 V
@3 Amp*
-5 V
@.25 Amp
*The +5 VIO and +4.3 V combined can not exceed 3 Amps.
Power Requirements
115/230 VAC +/- 15% @ .75 Amps, 47-63 Hz
24 VDC +/- 15% @ 2 Amps Max.
AC Power Loss Hold up time
8.3 mSec
RFI
Meets applicable FCC requirements for industrial equipment
EMI
Radiated Susceptibility
MS 461B RS03
Conducted Susceptibility
MS 461N CS02
Surge Withstand
IEEE 472_1974, ANSI C37.90a
Static Discharge
15kv to all exterior surfaces, connectors covered or terminated properly, mounted on grounded panel.
Environmental Operating Conditions
Environmental operating conditions
Humidity
0 - 95% non-condensing
Temperature
0 - 60°C
Temperature Storage
- 40 / +80 degrees C
Shock
+/- 10G’s, 11ms. 3pulses per axis
Vibration Sine
5 Hz to 50 Hz @ .0005 in D.A. 30min/axis
50 Hz to 500 Hz @ .625G2 30min/axis
Vibration Random
10 Hz to 50 Hz @ .029G2 /HZ
60 Hz to 300 Hz @ .029G2 -8db/octave
Altitude
10,000 ft max
Physical
Physical
Dimensions
(W x H x D)
3.53.in x 10.46in. x 8.25in.
(8.97cm x 26.59cm x 20.95cm)
Diagnostics
Power-up confidence tests
Run time confidence tests