Step
|
Action
|
---|---|
1
|
Insert eight AS–5B31006A voltage input packs.
|
2
|
Set all eight-position DIP switches to left (viewed from rear of module when held vertically). This setting selects eight channels.
|
3
|
Set two-position jumper so that pins T1, T2, and T3 (located below access hole on left side of module) are not jumpered. This setting selects four average.
|
4
|
Wire + side of field device to input terminal 3 (VIN HIGH).
|
5
|
Wire -side of field device to terminal 4 (VIN LOW) on AS–8535-000 high-density connector.
Note: Remove keying tabs on AS–8535–000 high density connector prior to installing module.
|
6
|
Determine which channel and slot locations are to be used.
|
7
|
Stop controller, remove power, and insert module in housing.
|
8
|
Reapply power
|
9
|
I/O map module as a B875, registers 30001—30008 binary.
|
10
|
Start controller.
|
11
|
Confirm that module’s active light is flashing.
Note: Active ON steady = OK. The active light may also be blinking for one of two reasons: the input to the module is out of range; the selected channel (SW1—SW8) has no input pack installed.
|
12
|
Call up appropriate mapped registers of B875 using programming panel.
|
13
|
Using measurable voltage source of field device, vary input voltage to B875. Compare these values to those in table below.
|
Voltage Input (V)
|
I/O Mapped Registers
|
Output Value
|
---|---|---|
-9.99
|
30001 =
|
0001
|
-5.00
|
30001 =
|
1024
|
0.00
|
30001 =
|
2048
|
+5.00
|
30001 =
|
3072
|
+9.99
|
30001 =
|
4095
|
Step
|
Action
|
---|---|
1
|
Insert eight fusible resistors shipped with AS–5B32001A input packs.
|
2
|
Insert eight current input packs (AS–5B32001A)
|
3
|
Set all eight-position DIP switches to left (viewed from rear of module when held vertically). This setting selects eight channels.
|
4
|
Set two-position jumper so that pins T1, T2, and T3 (located below access hole on left side of module) are not jumpered. This setting selects four average.
|
5
|
Wire input terminal 3 (VIN HIGH), 4 (VIN LOW) and 1 (CHASSIS GROUND) on AS–8535–000 high density connector as shown in typical field circuit connections for current inputs diagram, above.
Note: Remove keying tabs on AS–8535–000 high density connector prior to installing module.
|
6
|
Determine which channel and slot locations are to be used.
|
7
|
Stop controller, remove power, and insert module in housing.
|
8
|
Reapply power
|
9
|
I/O map module as a B875, registers 30001—30008 binary.
|
10
|
Start controller.
|
11
|
Confirm that module’s active light is flashing.
Note: Active ON steady = OK. The active light may also be blinking for one of two reasons: the input to the module is out of range; the selected channel (SW1—SW8) has no input pack installed.
|
12
|
Call up appropriate mapped registers of B875 using programming panel.
|
13
|
Using measurable voltage source of field device, vary input voltage to B875. Compare these values to those in table below.
|
Current Input (mA)
|
I/O Mapped Registers
|
Output Value
|
---|---|---|
4.01
|
30001 =
|
0001
|
8.00
|
30001 =
|
1024
|
12.00
|
30001 =
|
2048
|
16.00
|
30001 =
|
3072
|
19.99
|
30001 =
|
4095
|
Step
|
Action
|
---|---|
1
|
Insert eight voltage input packs (AS–5B40004A)
|
2
|
Set all eight-position DIP switches to left (viewed from rear of module when held vertically). This setting selects eight channels.
|
3
|
Set two-position jumper so that pins T1, T2, and T3 (located below access hole on left side of module) are not jumpered. This setting selects four average.
|
4
|
Wire input terminal 3 (VIN HIGH), 4 (VIN LOW) and 1 (CHASSIS GROUND) on AS–8535–000 high density connector as shown in typical field circuit connections for current inputs diagram, above.
Note: Remove keying tabs on AS–8535–000 high density connector prior to installing module.
|
5
|
Wire remaining inputs (2—8) in similar manner, connecting + to VIN HIGH and - to VIN LOW.
|
6
|
Determine which channel and slot locations are to be used.
|
7
|
Stop controller, remove power, and insert module in housing.
|
8
|
Reapply power
|
9
|
I/O map module as a B875, registers 30001—30008 binary.
|
10
|
Start controller.
|
11
|
Confirm that module’s active light is flashing.
Note: Active ON steady = OK. The active light may also be blinking for one of two reasons: the input to the module is out of range; the selected channel (SW1—SW8) has no input pack installed.
|
12
|
Call up appropriate mapped registers of B875 using programming panel.
|
13
|
Using measurable voltage source or field device, vary input voltage to B875. Compare these values to those in table below.
|
Current Input (mV)
|
I/O Mapped Registers
|
Output Value
|
---|---|---|
-9.99
|
30001 =
|
0001
|
-5.00
|
30001 =
|
1024
|
0.00
|
30001 =
|
2048
|
+5.00
|
30001 =
|
3072
|
+9.99
|
30001 =
|
4095
|