Step
|
Action
|
---|---|
1
|
Set the module configuration switch as follows: (viewing the rear of the module when held vertically)
The following table shows switch positions and their selection.
![]() |
2
|
Set voltage/current switches as follows:
|
3
|
Jumper input terminal 38 to terminal 3 and terminal 39 to terminal 4 on high-density connector AS–8535-000
Note: Terminals 38–39 are a voltage reference only (4.5000 Vdc); they should not be used for any other purpose.
Note: Remove the keying tabs on high-density connector AS–8535–000 prior to installation.
|
4
|
Determine which channel and slot location are being used for this module.
|
5
|
Stop controller. Turn power off, insert module and reapply power.
|
6
|
I/O map module as B875, registers 30001—30008 binary.
|
7
|
Start controller.
|
8
|
Observe that module’s active light is illuminated.
Note: Active on steady=O.K. Active blinking=O.K., but inputs may be out of range
|
9
|
Monitor input 30001. It should indicate 1843 decimal.
Note: 4096 format/10 V range=409.6 counts/V. 409.6X4.5000 Vdc = approximately 1843 decimal
|