Description
|
Analog output, D/A
|
Number of Points
|
4
|
Operating Range Voltage
|
0 - 5 Vdc, 0 - 10 Vdc, -5 to 5 Vdc, -10 to 10 Vdc; selectable per channel
|
Maximum Output Current
|
10 mA
|
Minimum Load
|
0-5 V= 500 Ω
0-10 V= 1 kΩ
-5 to +5 V= 500 Ω
-10 to +10 V=1 kΩ
|
Response Time to Within +/_0.1%
of Full Range
|
35 mS, all four channels
|
Valid Data Values
|
0 thru 4095
|
Resolution
|
1 part in 4096 counts
|
Accuracy***
Output Errors @ 25 °C (77 °F)
Overall
Nonlinearity
Differential Nonlinearity
*** All percentages are of full range.
|
+/-0.1% @ 25 °C absolute
+/-0.024%
+/-0.036%
|
Output Isolation
Output to OURBUS
Channel to Channel
|
1500 Vac or 2500 Vdc for 1 minute
500 Vac or 500 Vdc continuous operation
1500 Vac or 2500 Vdc for 1 minute
500 Vac or 500 Vdc continuous operation
|
Conversion
Resolution
Update Time
Settling Time
Linearity
Differential Nonlinearity
Crosstalk
|
12-bits (1 part in 4096)
The module can accept new data every
1 mS for a 4 channel update
Within +/-0.1%, < 350mS
0 to 60 °C, +/- 1 LSB maximum
0 to 60 °C, +/- 1.5 LSB maximum
-92 dB
|
Load Inductance
|
1 Henry max, with no external diode suppression
|
Power Required
+5 V
+4.3 V
-5 V
|
750 mA
5 mA
0 mA
|
Terminal Connector
|
AS-8535-000
|
Reference Type
|
Mapped as 4 registers output 4x
|
Output Type
|