Setting up a Quantum Hot Standby system involves a number of processes, summarized in the following paragraphs here and explained in detail elsewhere.
Mapping the Rack Extensions
A Quantum Hot Standby requires two racks with at least four slots. Map the two racks in an identical manner as described in
Identical Configurations.
Establishing the Primary CPU and Standby CPU Controllers
The Keypad may provide status information. Therefore, to view the status, use the Quantum Hot Standby CPU keypad by selecting Quantum PLC Operations → PLC Operations Hot Standby → Hot Standby Order.
Configuring in Control Expert
Using Control Expert, configure a network that is appropriate for the installed racks and the cabling.
Transferring and Sending the Program from Primary CPU to Standby CPU
Transfer the program from your PC to CPU using the Control Expert command PLC → Transfer program to PLC.
NOTE: During application program transfer, the system is not redundant.
After making sure that the primary CPU is in the RUN mode, send your program from the primary CPU to the standby CPU using the primary or standby CPU keypad. Select Quantum PLC Operations → PLC Operations Hot Standby → Hot Standby Transfer → Press <ENTER> to confirm Transfer.
NOTE: A program always goes from the Primary CPU controller to the other CPU controller.