Step
|
Action
|
---|---|
1
|
Verify that the Primary and Standby PLCs are in Run Primary CPU and Run Standby CPU modes.
|
2
|
Connect Control Expert to the Primary CPU.
|
3
|
Set the Command Register system bit %SW60.3 to 1.
|
4
|
Connect Control Expert to the Standby CPU controller.
|
5
|
Modify online the application program.
|
6
|
Perform a Rebuild All Project.
|
7
|
Verify that the Primary and Standby PLCs are in Run Primary CPU and Run Standby CPU modes.
|
8
|
Perform a Switchover.
Note: Standby CPU changes to Primary CPU.
|
9
|
Perform an application transfer to new Standby CPU.
|
10
|
Set the Command Register system bit %SW60.3 to 0.
Note: The Command Register system bit is then returned to 0 from 1.
|