Step
|
Action
|
|---|---|
|
1
|
Access the front panel keypad of a controller (Primary or Standby)
|
|
2
|
Go to PLC Operations menu
|
|
3
|
Go to Hot Standby submenu
|
|
4
|
Go to Hot Standby transfer and press ENTER to confirm the transfer.
NOTE: Verify that the transfer to Standby CPU occurs. |
|
Step
|
Action
|
|---|---|
|
1
|
Connect Control Expert to the Primary CPU.
|
|
2
|
Set Command Register system bit %SW60.5 to 1.
NOTE: This bit is reset 0 after the transfer. |