Step
|
Action
|
---|---|
1
|
Access the front panel keypad of the Primary CPU controller.
|
2
|
Go to PLC Operation menu.
|
3
|
Go to Hot Standby submenu.
|
4
|
Go to Hot Standby mode
|
5
|
Modify Run to Offline.
Note: Verify that Standby CPU switched to Primary CPU.
|
6
|
Modify Offline to run.
Note: Verify that the LCD displays Run Standby.
|
Step
|
Action
|
---|---|
1
|
Open file 1 in Control Expert.
|
2
|
Connect Control Expert to the Primary CPU.
|
3
|
Verify the A/B controller order of the Primary CPU.
|
4
|
Set correct bit in %SW60:
|
5
|
Open file 2.
|
6
|
Connect Control Expert to the new Primary CPU controller.
|
7
|
Set Command Register system bit used in Step 4 to 1.
NOTE: Verify that the Standby PLC is now online. |
8
|
Verify that both Primary and Standby CPUs are in Run Primary CPU and Run Standby CPU modes.
|