Quantum Hot Standby Operation Modes
Original instructions
Operating Modes Overview
In a normally operating Quantum Hot Standby system, there are two PLCs running, one as the Primary PLC and one as the Standby PLC. Consequently, a Quantum Hot Standby system requires additional states to reflect the system status. The redundant nature of the system means that the relationships between operating modes changes. The following provides a quick summary of the Quantum Hot Standby operating modes and states.
WARNING
UNINTENDED EQUIPMENT OPERATION
Verify the PLC operating mode before installing, operating, modifying, or servicing it.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Before acting on a PLC, positively confirm the operating mode of both Hot PLCs by viewing their LCD displays, LEDs or System Status Words.
Before running a Quantum Hot Standby system that uses an Ethernet I/O Head, ensure that a least one CRA Drop has established communication with CRP Head module.
This information is accessible through:
Without communication established, the CPU goes to RUN OFFLINE instead of the PRIMARY RUN or STANDBY RUN mode.
For a more detailed description of the Quantum Hot Standby operating modes, including a state transitions diagram, refer to Operating Modes.
STOP Mode
In the STOP mode the PLC has both:
RUN Mode
There are 2 Hot Standby states in the RUN mode:
NOTE: For information about A/B PLC assignment, refer to Distinguishing Between Controllers.
OFFLINE Mode
In the OFFLINE mode the PLC has:
Non-Configured State
In certain circumstances, such as when no valid application is loaded on a PLC, a Hot Standby controller enters (and report itself) as being in a "Non-Conf" (non-configured state), which is not considered as an operating mode.