In a normally operating Quantum Hot Standby system, there are two PLCs running, one as the Primary PLC and one as the Standby PLC. Consequently, a Quantum Hot Standby system requires additional states to reflect the system status. The redundant nature of the system means that the relationships between operating modes changes. The following provides a quick summary of the Quantum Hot Standby operating modes and states.
Before acting on a PLC, positively confirm the operating mode of both Hot PLCs by viewing their LCD displays, LEDs or System Status Words.
Before running a Quantum Hot Standby system that uses an Ethernet I/O Head, ensure that a least one CRA Drop has established communication with CRP Head module.
This information is accessible through:
Without communication established, the CPU goes to RUN OFFLINE instead of the PRIMARY RUN or STANDBY RUN mode.
For a more detailed description of the Quantum Hot Standby operating modes, including a state transitions diagram, refer to
Operating Modes.
In the STOP mode the PLC has both:
-
received a Stop command
-
successfully stopped
There are 2 Hot Standby states in the RUN mode:
-
Primary state
The PLC has both:
-
Standby state
The PLC has:
In the OFFLINE mode the PLC has:
In certain circumstances, such as when no valid application is loaded on a PLC, a Hot Standby controller enters (and report itself) as being in a "Non-Conf" (non-configured state), which is not considered as an operating mode.