Power consumption breakdown
(Original Document)
Table 3
This table shows the typical power consumption of each module and can be used to calculate the power consumption per rack and on each output depending on the modules installed:
Module type
Product references
Consumption in mA (typical value) (1)
At 5VDC
At 24 VR
At 24VS (2)
Analog
TSX AEY 414
660
TSX AEY 420
500
TSX AEY 800
270
TSX AEY 810
475
TSX AEY 1600
270
TSX AEY 1614
300
TSX AEY 410
990
TSX AEY 800 (3)
200
300
Counting
TSX CTY 2A
280
30
TSX CTY 2C
850
15
TSX CTY 4A
330
36
Axis control
TSX CAY 21
1100
15
TSX CAY 22
1100
15
TSX CAY 41
1500
30
TSX CAY 42
1500
30
TSX CAY 33
1500
30
Step by step control
TSX CFY 11
510
50
TSX CFY 21
650
100
Weighing
TSX ISPY 100 (3)
150
145
(1) Module consumption is given for 100% of inputs or outputs in state 1.
(2) If using a 24V (direct) external sensor supply, the consumption on this output should not be taken into account when selecting the power supply for the rack.
(3) If using a 24VR (direct) external power supply, the consumption of power on the internal 24VR should not be taken into account when selecting the rack power supply.