Power Consumption Breakdown
(Original Document)
Table 4
This table shows the typical power consumption of each module and can be used to calculate the power consumption per rack and on each output depending on the modules installed:
Module type
Product references
Consumption in mA (typical value) (1)
At 5VDC
At 24 VR
At 24VS (2)
Communication
TSX ETY 110 (3)
(4)
800
1200
TSX ETY 120 (3)
(4)
800
1200
TSX ETY 210 (3)
(4)
800
1200
TSX IBY 100
500
TSX PBY 100
400
TSX SAY 100
110
TSX SCY 21601
350
TSX SCP 111
140
TSX SCP 112
120
TSX SCP 114
150
TSX FPP 10
330
TSX FPP 20
330
TSX JNP 112
120
TSX JNP 114
150
TSX MBP 100
220
TSX MDM 10
195
(1) Module consumption is given for 100% of inputs or outputs in state 1,
(2) If using a 24V (direct) external sensor power supply, the consumption on this output should not be taken into account when selecting the power supply for the rack,
(3) Without remote power feed (RJ45),