Power consumption breakdown
(Original Document)
Table 2
This table shows the typical power consumption of each module and can be used to calculate the consumption per rack and on each output depending on the modules installed:
Module type
Product references
Consumption in mA (typical value) (1)
At 5VDC
At 24 VR
At 24VC (2)
Discrete outputs
TSX DSY 08R4D
55
80
TSX DSY 08R5
55
70
TSX DSY 08R5A
55
80
TSX DSY 08S5
125
TSX DSY 08T2
55
TSX DEY 08T22
55
TSX DEY 08T31
55
TSX DEY 16R5
80
135
TSX DEY 16S4
220
TSX DEY 16S5
220
TSX DEY 16T2
80
TSX DEY 16T3
80
TSX DSY 32T2K
140
TSX DSY 64T2K
155
Discrete Inputs/Outputs
TSX DMY 28FK
300
75
TSX DMY 28RFK
300
75
Emergency stop backup
TSX PAY 262
150
TSX PAY 282
150
Remote X-Bus
TSX REY 200
500
(1) Module consumption is given for 100% of inputs or outputs in state 1.
(2) If using a 24V (direct) external sensor supply, the consumption on this output should not be taken into account when selecting the power supply for the rack.