Reference
|
|||
---|---|---|---|
![]() |
|||
Primary
|
Nominal voltage
|
24 Vdc
|
|
Voltage limits (including ripple) (1) (possible up to 34 V for 1hour in every 24 hours)
|
19.2 to 30 Vdc
|
||
Nominal input current: Irms at 24 VDC
|
≤2.7 A
|
||
Initial power-up at 25°C (2)
|
I
signal
|
≤ 150 A at 24 Vdc
|
|
I2t
on locking
|
26 A2s
|
||
It
on locking
|
0.3 As
|
||
Accepted length of micro-power outages
|
≤1 ms
|
||
Integrated input protection
|
no
|
||
Secondary
|
Total output (typical)
|
50 W
|
|
5VDC output
|
Nominal voltage:
|
5.1 V
|
|
Nominal current
|
7 A
|
||
Power (typical)
|
35 W
|
||
24 VR output (24 V relay) (3)
|
Nominal voltage:
|
U network – 0.6 V
|
|
Nominal current
|
0.8 A
|
||
Power (typical)
|
19 W
|
||
Built-in output protection against
(4)
|
Overloading
|
yes
|
|
Short circuits
|
yes
|
||
Over-voltage
|
yes
|
||
Power dissipation
|
15 W
|
||
Auxiliary functions
|
|||
Alarm relay
|
yes (1 contact closed, free from potential on terminal block)
|
||
Display
|
yes, via LED on front panel
|
||
Back-up battery
|
yes (status monitored via LED on front panel of module)
|
||
Conformity to the norms
|
IEC1131-2
|