Reference
|
|||
---|---|---|---|
![]() |
|||
Primary
|
Nominal voltage
|
24..0.48 Vdc
|
|
Voltage limits (including ripple)
|
19.2 to 60 Vdc
|
||
Nominal input current: Irms
|
≤ 3 A at 24 Vdc
≤ 1.5 A at 48 Vdc
|
||
Initial power-up at 25°C (1)
|
I
signal
|
≤ 15 A at 24 Vdc
≤ 15 A at 48 Vdc
|
|
I2t
on locking
|
2.2 A2s at 24 Vdc
1.8 A2s at 48 Vdc
|
||
It
on locking
|
0.25 As at 24 Vdc
0.15 As at 48 Vdc
|
||
Accepted length of micro-power outages
|
≤1 ms
|
||
Built-in protection of + input
|
by internal, non-accessible fuse module
|
||
Secondary
|
Total output (typical)
|
50 W
|
|
5VDC output
|
Nominal voltage:
|
5.1 V
|
|
Nominal current
|
7 A
|
||
Power (typical)
|
35 W
|
||
24 VR output (24 Vdc relay) (2)
|
Nominal voltage:
|
24 V
|
|
Nominal current
|
0.8 A
|
||
Power (typical)
|
19 W
|
||
Built-in output protection against
|
Overloading
|
yes
|
|
Short circuits
|
yes
|
||
Over-voltage
|
yes
|
||
Power dissipation
|
20 W
|
||
Auxiliary functions
|
|||
Alarm relay
|
yes (1 contact closed, free from potential on terminal block)
|
||
Display
|
yes, via LED on front panel
|
||
Back-up battery
|
yes (status monitored via LED on front panel of module)
|
||
Conformity to the norms
|
IEC1131-2
|
||
Insulation
|
Dielectric resistance
|
primary/secondary
primary/ground
|
2000 Vrms-50/60Hz-1mn
2000 Vrms-50/60Hz-1mn
|
Resistance of insulation
|
primary/secondary
primary/ground
|
≥ 10 MΩ
≥ 10 MΩ
|