 Reference             
 | 
|||
|---|---|---|---|
![]()  | 
|||
| 
 Primary             
 | 
 Nominal voltage             
 | 
 24..0.48 Vdc             
 | 
|
| 
 Voltage limits (including ripple)             
 | 
 19.2 to 60 Vdc             
 | 
||
| 
 Nominal input current: Irms             
 | 
 ≤ 3 A at 24 Vdc             
≤ 1.5 A at 48 Vdc             
 | 
||
| 
 Initial power-up at 25°C (1)             
 | 
 I             
signal             
 | 
 ≤ 15 A at 24 Vdc             
≤ 15 A at 48 Vdc             
 | 
|
| 
 I2t             
on locking             
 | 
 2.2 A2s at 24 Vdc             
1.8 A2s at 48 Vdc             
 | 
||
| 
 It             
on locking             
 | 
 0.25 As at 24 Vdc             
0.15 As at 48 Vdc             
 | 
||
| 
 Accepted length of micro-power outages             
 | 
 ≤1 ms             
 | 
||
| 
 Built-in protection of + input             
 | 
 by internal, non-accessible fuse module             
 | 
||
| 
 Secondary             
 | 
 Total output (typical)             
 | 
 50 W             
 | 
|
| 
 5VDC output             
 | 
 Nominal voltage:             
 | 
 5.1 V             
 | 
|
| 
 Nominal current             
 | 
 7 A             
 | 
||
| 
 Power (typical)             
 | 
 35 W             
 | 
||
| 
 24 VR output (24 Vdc relay) (2)             
 | 
 Nominal voltage:             
 | 
 24 V             
 | 
|
| 
 Nominal current             
 | 
 0.8 A             
 | 
||
| 
 Power (typical)             
 | 
 19 W             
 | 
||
| 
 Built-in output protection against             
 | 
 Overloading             
 | 
 yes             
 | 
|
| 
 Short circuits             
 | 
 yes             
 | 
||
| 
 Over-voltage             
 | 
 yes             
 | 
||
| 
 Power dissipation             
 | 
 20 W            
 | 
||
| 
 Auxiliary functions            
 | 
|||
| 
 Alarm relay            
 | 
 yes (1 contact closed, free from potential on terminal block)            
 | 
||
| 
 Display            
 | 
 yes, via LED on front panel            
 | 
||
| 
 Back-up battery            
 | 
 yes (status monitored via LED on front panel of module)            
 | 
||
| 
 Conformity to the norms            
 | 
 IEC1131-2            
 | 
||
| 
 Insulation            
 | 
 Dielectric resistance            
 | 
 primary/secondary            
primary/ground            
 | 
 2000 Vrms-50/60Hz-1mn            
2000 Vrms-50/60Hz-1mn            
 | 
| 
 Resistance of insulation            
 | 
 primary/secondary            
primary/ground            
 | 
 ≥ 10 MΩ            
≥ 10 MΩ            
 | 
|