 Reference             
 | 
 TSX PSY 1610             
 | 
||
|---|---|---|---|
![]()  | 
|||
| 
 Primary             
 | 
 Nominal voltage (not isolated)              
 | 
 24 VDC             
 | 
|
| 
 Voltage limits (including ripple) (1) (possible up to 34 V for 1 hour in every 24 hours)             
 | 
 19.2 to 30 Vdc             
 | 
||
| 
 Nominal input current: Irms at 24 Vdc             
 | 
 ≤1.5 A             
 | 
||
| 
 Initial power-up at 25°C (2)             
 | 
 I             
signal             
 | 
 ≤ 100A at 24 Vdc             
 | 
|
| 
 I2t             
on locking             
 | 
 6 A2s             
 | 
||
| 
 It             
on locking             
 | 
 0.1 As             
 | 
||
| 
 Accepted length of micro-power outages             
 | 
 ≤1 ms             
 | 
||
| 
 Integrated input protection             
 | 
 via 5x20 time delay fuse, 3.5 A             
 | 
||
| 
 Secondary             
 | 
 Total output (typical)             
 | 
 30 W             
 | 
|
| 
 5VDC output             
 | 
 Nominal voltage:             
 | 
 5 V             
 | 
|
| 
 Nominal current             
 | 
 3 A             
 | 
||
| 
 Power (typical)             
 | 
 15 W             
 | 
||
| 
 24VR output (24VDC relay) (3)             
 | 
 Nominal voltage:             
 | 
 U network – 0.6 V             
 | 
|
| 
 Nominal current             
 | 
 0.6 A             
 | 
||
| 
 Power (typical)             
 | 
 15 W             
 | 
||
| 
 Built-in output protection against (4)             
 | 
 Overloading             
 | 
 yes             
 | 
|
| 
 Short circuits             
 | 
 yes             
 | 
||
| 
 Over-voltage             
 | 
 yes             
 | 
||
| 
 Power dissipation             
 | 
 10 W             
 | 
||
| 
 Auxiliary functions             
 | 
|||
| 
 Alarm relay             
 | 
 yes (1 contact closed, free from potential on terminal block)             
 | 
||
| 
 Display             
 | 
 yes, via LED on front panel             
 | 
||
| 
 Back-up battery             
 | 
 yes (status monitored via LED on front panel of module)             
 | 
||
| 
 Conformity to the norms             
 | 
 IEC1131-2             
 | 
||