TSX PSY 8500 power supply module
(Original Document)
Characteristics
The TSX PSY 8500 module is a double format alternating current power supply module.
Reference
Primary
Nominal voltage (V) ~
100..120/200..240
Voltage limits (V) ~
85..140/170..264
Nominal and limit frequencies
50-60/47-63Hz
Apparent power
150 VA
Nominal current consumption: Irms
≤ 1.4A to 100V
≤ 0.5A to 240V
Initial power-up at 25°C (1)
I
signal
≤ 30A to 100V
≤ 60A to 240V
I2t
on locking
15A2s to 100V
8A2s to 240V
It
on locking
0.15 As at 100V
0.15 As at 240V
Accepted length of micro-power outages
≤10ms
Integrated phase protection
via internal, non-accessible fuse
Secondary
Total output
77/85/100W (2)
5VDC output
Nominal voltage:
5.1V
Nominal current
15A
Power (typical)
75W
24VR output (24V relay) (3)
Nominal voltage:
not supplied
Nominal current
not supplied
Power (typical)
not supplied
24VS output (24V sensor)
Nominal voltage:
24VDC
Nominal current
1.6A
Power (typical)
38W
Protection of output from
overloading/short circuits/over-voltages
Power dissipation
20W
Auxiliary functions
Alarm relay
yes (1 contact closed, free from potential on terminal block)
Display
yes, via LED on front panel
Back-up battery
yes (status monitored via LED on front panel of module)
Conformity to the norms
IEC 1131-2
Insulation
Dielectric resistance (50/60Hz-1mn)
Primary/secondary
3000 Vrms
Primary/ground
3000 Vrms
24VDC output/ground
500 Vrms
Resistance of insulation
Primary/secondary
≥ 100 MΩ
Primary/ground
≥ 100 MΩ
(1) These values should be taken into account when starting up several devices at the same time, or for dimensioning the protection systems.
(2) 77W at 60°C, 85W at 55°C, 100W at 55°C, if the rack is fitted with ventilation modules.
(3) 24V direct current output for supplying relays of "relay output" modules.