Reference
|
|||
---|---|---|---|
![]() |
|||
Primary
|
Nominal voltage (V) ~
|
100..120/200..240
|
|
Voltage limits (V) ~
|
85..140/170..264
|
||
Nominal and limit frequencies
|
50-60/47-63Hz
|
||
Apparent power
|
150 VA
|
||
Nominal current consumption: Irms
|
≤ 1.4A to 100V
≤ 0.5A to 240V
|
||
Initial power-up at 25°C (1)
|
I
signal
|
≤ 30A to 100V
≤ 60A to 240V
|
|
I2t
on locking
|
15A2s to 100V
8A2s to 240V
|
||
It
on locking
|
0.15 As at 100V
0.15 As at 240V
|
||
Accepted length of micro-power outages
|
≤10ms
|
||
Integrated phase protection
|
via internal, non-accessible fuse
|
||
Secondary
|
Total output
|
77/85/100W (2)
|
|
5VDC output
|
Nominal voltage:
|
5.1V
|
|
Nominal current
|
15A
|
||
Power (typical)
|
75W
|
||
24VR output (24V relay) (3)
|
Nominal voltage:
|
not supplied
|
|
Nominal current
|
not supplied
|
||
Power (typical)
|
not supplied
|
||
24VS output (24V sensor)
|
Nominal voltage:
|
24VDC
|
|
Nominal current
|
1.6A
|
||
Power (typical)
|
38W
|
||
Protection of output from
|
overloading/short circuits/over-voltages
|
||
Power dissipation
|
20W
|
||
Auxiliary functions
|
|||
Alarm relay
|
yes (1 contact closed, free from potential on terminal block)
|
||
Display
|
yes, via LED on front panel
|
||
Back-up battery
|
yes (status monitored via LED on front panel of module)
|
||
Conformity to the norms
|
IEC 1131-2
|
||
Insulation
|
Dielectric resistance (50/60Hz-1mn)
|
Primary/secondary
|
3000 Vrms
|
Primary/ground
|
3000 Vrms
|
||
24VDC output/ground
|
500 Vrms
|
||
Resistance of insulation
|
Primary/secondary
|
≥ 100 MΩ
|
|
Primary/ground
|
≥ 100 MΩ
|