 Reference             
 | 
|||
|---|---|---|---|
![]()  | 
|||
| 
 Primary             
 | 
 Nominal voltage (V) ~             
 | 
 100..120/200..240             
 | 
|
| 
 Voltage limits (V) ~             
 | 
 85..140/170..264             
 | 
||
| 
 Nominal and limit frequencies             
 | 
 50-60/47-63Hz             
 | 
||
| 
 Apparent power             
 | 
 150 VA             
 | 
||
| 
 Nominal current consumption: Irms             
 | 
 ≤ 1.4A to 100V             
≤ 0.5A to 240V             
 | 
||
| 
 Initial power-up at 25°C (1)             
 | 
 I             
signal             
 | 
 ≤ 30A to 100V             
≤ 60A to 240V             
 | 
|
| 
 I2t             
on locking             
 | 
 15A2s to 100V             
8A2s to 240V             
 | 
||
| 
 It             
on locking             
 | 
 0.15 As at 100V             
0.15 As at 240V             
 | 
||
| 
 Accepted length of micro-power outages             
 | 
 ≤10ms             
 | 
||
| 
 Integrated phase protection             
 | 
 via internal, non-accessible fuse             
 | 
||
| 
 Secondary             
 | 
 Total output             
 | 
 77/85/100W (2)             
 | 
|
| 
 5VDC output             
 | 
 Nominal voltage:             
 | 
 5.1V             
 | 
|
| 
 Nominal current             
 | 
 15A             
 | 
||
| 
 Power (typical)             
 | 
 75W             
 | 
||
| 
 24VR output (24V relay) (3)             
 | 
 Nominal voltage:             
 | 
 not supplied             
 | 
|
| 
 Nominal current             
 | 
 not supplied             
 | 
||
| 
 Power (typical)             
 | 
 not supplied             
 | 
||
| 
 24VS output (24V sensor)             
 | 
 Nominal voltage:             
 | 
 24VDC             
 | 
|
| 
 Nominal current             
 | 
 1.6A             
 | 
||
| 
 Power (typical)             
 | 
 38W             
 | 
||
| 
 Protection of output from             
 | 
 overloading/short circuits/over-voltages             
 | 
||
| 
 Power dissipation             
 | 
 20W             
 | 
||
| 
 Auxiliary functions             
 | 
|||
| 
 Alarm relay             
 | 
 yes (1 contact closed, free from potential on terminal block)             
 | 
||
| 
 Display             
 | 
 yes, via LED on front panel             
 | 
||
| 
 Back-up battery             
 | 
 yes (status monitored via LED on front panel of module)             
 | 
||
| 
 Conformity to the norms             
 | 
 IEC 1131-2             
 | 
||
| 
 Insulation             
 | 
 Dielectric resistance (50/60Hz-1mn)             
 | 
 Primary/secondary             
 | 
 3000 Vrms             
 | 
| 
 Primary/ground             
 | 
 3000 Vrms             
 | 
||
| 
 24VDC output/ground             
 | 
 500 Vrms             
 | 
||
| 
 Resistance of insulation             
 | 
 Primary/secondary             
 | 
 ≥ 100 MΩ             
 | 
|
| 
 Primary/ground             
 | 
 ≥ 100 MΩ             
 | 
||