 Reference              
 | 
|||
|---|---|---|---|
![]()  | 
|||
| 
 Primary              
 | 
 Nominal voltage (V) ~              
 | 
 100..120/200..240              
 | 
|
| 
 Voltage limits (V) ~              
 | 
 85..140/190..264              
 | 
||
| 
 Nominal and limit frequencies              
 | 
 50-60/47-63Hz              
 | 
||
| 
 Apparent power              
 | 
 150 VA              
 | 
||
| 
 Nominal current consumption: Irms              
 | 
 ≤ 1.7A to 100V              
≤ 0.5A to 240V              
 | 
||
| 
 Initial power-up at 25°C (1)              
 | 
 I              
signal              
 | 
 ≤ 38A to 100V              
≤ 38A to 240V              
 | 
|
| 
 I2t              
on locking              
 | 
 4A2s to 100V              
2A2s to 240V              
 | 
||
| 
 It              
on locking              
 | 
 0.11 As at 100V              
0.11 As at 240V              
 | 
||
| 
 Accepted length of micro-power outages              
 | 
 ≤10ms              
 | 
||
| 
 Integrated phase protection              
 | 
 via internal, non-accessible fuse              
 | 
||
| 
 Secondary              
 | 
 Total output              
 | 
 50W              
 | 
|
| 
 5VDC output              
 | 
 Nominal voltage:              
 | 
 5.1V              
 | 
|
| 
 Nominal current              
 | 
 7A              
 | 
||
| 
 Power (typical)              
 | 
 35W              
 | 
||
| 
 24VR output (24V relay) (2)              
 | 
 Nominal voltage:              
 | 
 24VCC              
 | 
|
| 
 Nominal current              
 | 
 0.8A              
 | 
||
| 
 Power (typical)              
 | 
 19W              
 | 
||
| 
 24VS output (24V sensor)              
 | 
 Nominal voltage:              
 | 
 24VCC              
 | 
|
| 
 Nominal current              
 | 
 0.8A              
 | 
||
| 
 Power (typical)              
 | 
 19W              
 | 
||
| 
 Protection of output from              
 | 
 overloading/short circuits/over-voltages              
 | 
||
| 
 Power dissipation              
 | 
 20W              
 | 
||
| 
 Auxiliary functions              
 | 
|||
| 
 Alarm relay              
 | 
 yes (1 contact closed, free from potential on terminal block)              
 | 
||
| 
 Display              
 | 
 yes, via LED on front panel              
 | 
||
| 
 Back-up battery              
 | 
 yes (status monitored via LED on front panel of module)              
 | 
||
| 
 Conformity to the norms              
 | 
 IEC 1131-2              
 | 
||
| 
 Insulation              
 | 
 Dielectric resistance (50/60Hz-1mn)              
 | 
 Primary/secondary              
 | 
 2000 Vrms              
 | 
| 
 Primary/ground              
 | 
 2000 Vrms              
 | 
||
| 
 24VDC output/ground              
 | 
 -              
 | 
||
| 
 Resistance of insulation              
 | 
 Primary/secondary              
 | 
 ≥ 100 MΩ              
 | 
|
| 
 Primary/ground              
 | 
 ≥ 100 MΩ              
 | 
||