TSX PSY 5500 power supply module
(Original Document)
Characteristics
The TSX PSY 5500 module is a double format alternating current power supply module.
Reference
Primary
Nominal voltage (V) ~
100..120/200..240
Voltage limits (V) ~
85..140/190..264
Nominal and limit frequencies
50-60/47-63Hz
Apparent power
150 VA
Nominal current consumption: Irms
≤ 1.7A to 100V
≤ 0.5A to 240V
Initial power-up at 25°C (1)
I
signal
≤ 38A to 100V
≤ 38A to 240V
I2t
on locking
4A2s to 100V
2A2s to 240V
It
on locking
0.11 As at 100V
0.11 As at 240V
Accepted length of micro-power outages
≤10ms
Integrated phase protection
via internal, non-accessible fuse
Secondary
Total output
50W
5VDC output
Nominal voltage:
5.1V
Nominal current
7A
Power (typical)
35W
24VR output (24V relay) (2)
Nominal voltage:
24VCC
Nominal current
0.8A
Power (typical)
19W
24VS output (24V sensor)
Nominal voltage:
24VCC
Nominal current
0.8A
Power (typical)
19W
Protection of output from
overloading/short circuits/over-voltages
Power dissipation
20W
Auxiliary functions
Alarm relay
yes (1 contact closed, free from potential on terminal block)
Display
yes, via LED on front panel
Back-up battery
yes (status monitored via LED on front panel of module)
Conformity to the norms
IEC 1131-2
Insulation
Dielectric resistance (50/60Hz-1mn)
Primary/secondary
2000 Vrms
Primary/ground
2000 Vrms
24VDC output/ground
-
Resistance of insulation
Primary/secondary
≥ 100 MΩ
Primary/ground
≥ 100 MΩ
(1) These values should be taken into account when starting up several devices at the same time, or for dimensioning the protection systems.
(2) 24V direct current output for supplying relays of "relay output" modules.