TSX PSY 2600 power supply module
(Original Document)
Characteristics
The TSX PSY 2600 module is a single format alternating current power supply module.
Reference
TSX PSY 2600
Primary
Nominal voltage (V) ~
100...240
Voltage limits (V) ~
85...264
Nominal and limit frequencies
50-60/47-63Hz
Apparent power
50 VA
Nominal current consumption: Irms
≤ 0.5A to 100V
≤ 0.3A to 240V
Initial power-up at 25°C (1)
I
signal
≤ 37A to 100V
≤ 75A to 240V
I2t
on locking
0.63A2s to 100V
2.6A2s to 240V
It
on locking
0.034 As at 100V
0.067 As at 240V
Accepted length of micro-power outages
≤10ms
Integrated phase protection
via internal, non-accessible fuse
Secondary
Total output
26W
5VDC output
Nominal voltage:
5.1V
Nominal current
5A
Power (typical)
25W
24VR output (24V relay) (2)
Nominal voltage:
24VDC
Nominal current
0.6A
Power (typical)
15W
24VS output (24V sensor)
Nominal voltage:
24VDC
Nominal current
0.5A
Power (typical)
12W
Protection of output from
overloading/short circuits/over-voltages
Power dissipation
10W
Auxiliary functions
Alarm relay
yes (1 contact closed, free from potential on terminal block)
Display
yes, via LED on front panel
Back-up battery
yes (status monitored via LED on front panel of module)
Conformity to the norms
IEC 1131-2
Insulation
Dielectric resistance (50/60Hz-1mn)
Primary/secondary
2000 Vrms
Primary/ground
2000 Vrms
24VDC output/ground
-
Resistance of insulation
Primary/secondary
≥ 100 MΩ
Primary/ground
≥ 100 MΩ
(1) These values should be taken into account when starting up several devices at the same time, or for dimensioning the protection systems.