Rack number:
|
|||
---|---|---|---|
1
|
Power required at 5V DC output:
|
(1)...x10-3Ax5V
|
=................W
|
2
|
Power required at 24 VR output:
|
(1)...x10-3Ax5V
|
=................W
|
3
|
Power required at 24 VS output:
|
(1)...x10-3Ax5V
|
=................W
|
4
|
Total power required:
|
=................W
|
![]() |
UNEXPECTED EQUIPMENT BEHAVIOR
When selecting the power supply module, ensure that the available power on each output (5 VDC, 24 VR and 24 VDC), and the total available power, are superior to the consumption needs computed through the breakdown of power method.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
On 5V DC output
|
On 24 VR output
|
On 24 VS output
|
Total
|
|
---|---|---|---|---|
TSX PSY 1610
|
15 W
|
15 W
|
-
|
30 W
|
TSX PSY 2600
|
25 W
|
15 W
|
12 W
|
26 W
|
TSX PSY 3610
|
35 W
|
19 W
|
-
|
50 W
|
TSX PSY 5520
|
35 W
|
19 W
|
-
|
50 W
|
TSX PSY 5500
|
35 W
|
19 W
|
19 W
|
50 W
|
TSX PSY 8500
|
75 W
|
-
|
38 W
|
77/85/100W (1)
|