Module Type
|
32 IN (4 groups x 8 points) individually isolated
|
External Power
|
Not required for this module
|
Power Dissipation
|
9 W (max)
|
Bus Current required
|
250 mA
|
I/O map
|
2 input word
|
Fault Detection
|
None
|
50 Hz
|
ON: 175 ... 264 VAC (9.7 mA max)
OFF: 0 ... 40 VAC
|
60 Hz
|
ON: 165 ... 264 VAC (11.5 mA max)
OFF: 0 ... 40 VAC
* Do not use outside the 47 ... 63 Hz range
|
Maximum Allowable Leakage Current from an External Device to be recognized as an OFF Condition.
|
2.6 mA
|
50 Hz
|
32 kohms capacitive
|
60 Hz
|
27 kohms capacitive
|
Input to Input
|
1780 VAC for 1 minute
|
Input to Bus
|
1780 VAC for 1 minute
|
Continuous
|
264 VAC
|
10 s
|
300 VAC
|
1 Cycle
|
400 VAC
|
OFF - ON
|
Min: 4.9 ms. Max: 0.75 line cycle.
|
ON - OFF
|
Min: 7.3 ms. Max: 12.3 ms.
|
Internal
|
None
|
External
|
User installed per local and national electrical codes
|