Module Type
|
16 OUT (1 group x 16 channels)
|
Logic
|
True High
|
Pre-actuator Power Supply
|
24 VDC
|
Power Dissipation
|
1.9 W + 0.65 V x I2
|
Bus Current required (Module)
|
350 mA
|
I/O map
|
4 output words and 7 input words
|
Fault Detection
|
|
Update Time
|
15 ms for all channels
|
Operating Voltage (max.)
|
19.2 ... 30 VDC
|
Absolute Voltage (max.)
|
34 VDC
|
ON State Drop / Point
|
0.3 VDC @ 0.5 A
|
Each Point
|
0.65 A
|
Per Module
|
10.4 A
|
Surge Current (max.)
|
2 A @ 10 ms once (internal current limitation)
|
OFF State Leakage / Point
|
0.5 mA @ 30 VDC
|
Group to Group
|
N/A
|
Group to Bus
|
1500 VAC rms for 1 minute
|
Output Protection
|
|
OFF - ON
|
20 ms (max.)
|
ON - OFF
|
20 ms (max.)
|
Load Inductance (max.)
|
0.5 Henry @ 11 Hz switch frequency, or:
![]() |
Load Capacitance (max.)
|
50 μF
|
Internal
|
None
|
External
|
Mandatory
(fast blow, max 10 A, determined by the module load current)
|
![]() |
OVERCURRENT TO THE OUPUTS
Use fast acting fuses to protect the electronic components of the module from overcurrent. Improper fuse selection could result to damage to the module.
Failure to follow these instructions can result in injury or equipment damage.
|