Specifications
Original instructions
General Specifications
General Specifications
Module Type
16 OUT (1 group x 16 channels)
Logic
True High
Pre-actuator Power Supply
24 VDC
Power Dissipation
1.9 W + 0.65 V x I2
Bus Current required (Module)
350 mA
I/O map
4 output words and 7 input words
Fault Detection
  • overload
  • 24 V process supply problem
  • system inoperable
Update Time
15 ms for all channels
Voltage
Voltage
Operating Voltage (max.)
19.2 ... 30 VDC
Absolute Voltage (max.)
34 VDC
ON State Drop / Point
0.3 VDC @ 0.5 A
Maximum Load Current / Surge Current
Maximum Load Current / Surge Current
Each Point
0.65 A
Per Module
10.4 A
Surge Current (max.)
2 A @ 10 ms once (internal current limitation)
OFF State Leakage / Point
0.5 mA @ 30 VDC
Isolation / Protection
Isolation / Protection
Group to Group
N/A
Group to Bus
1500 VAC rms for 1 minute
Output Protection
  • transient voltage suppression (internal)
  • overload
  • disjunction (0.7 A @ 10 ms)
  • current limitation (2 A)
Response (Resistive Loads)
Response (Resistive Loads)
OFF - ON
20 ms (max.)
ON - OFF
20 ms (max.)
Load Inductance / Capacitance (max.)
Load Inductance / Capacitance (max.)
Load Inductance (max.)
0.5 Henry @ 11 Hz switch frequency, or:
Load Capacitance (max.)
50 μF
Fuses
Fuses
Internal
None
External
Mandatory
(fast blow, max 10 A, determined by the module load current)
CAUTION
OVERCURRENT TO THE OUPUTS
Use fast acting fuses to protect the electronic components of the module from overcurrent. Improper fuse selection could result to damage to the module.
Failure to follow these instructions can result in injury or equipment damage.