Altitude Operating Conditions

The characteristics in the table below apply to the modules BMX DAI 0805 and BMX DAI 0805H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.

For detailed information, refer to chapter Operating and Storage Conditions.

General Characteristics

This table presents the general characteristics for the BMX DAI 0805 and BMX DAI 0805H module:

Module type

200...240 VAC inputs

Operating temperature

BMX DAI 0805

0...60 ºC (32...140 ºF)

BMX DAI 0805H

-25...70 ºC (-13...158 ºF)

Absolute maximum input

Continuous

264 VAC

10s

300 VAC

1 cycle

400 VAC

Nominal input values

Voltage

200...240 VAC

Current

10.40 mA (for U=220 V at 50 Hz)

Frequency

50/60Hz

Threshold input values

At 1

Voltage

≥ 159 V

Current

> 6 mA (for U=159)

At 0

Voltage

≤ 40 V

Current

≤ 4 mA

Frequency

47 Hz to 63 Hz

Sensor supply (including ripple)

170...264 V

Peak of current on enabling (at nominal U)

480 mA

Input impedance

at nominal U and f = 55 Hz

21 kΩ

Response time

Activation

10 ms

Deactivation

20 ms

Input type

Capacitive

Input type in compliance with IEC 61131-2 standard

Type 2

2-wire / 3-wire proximity sensor compatibility (IEC 60947-5-2 standard compliant)

2-wire (AC)

Reliability

MTBF for continuous operation in hours at ambient temperature 30 °C (86 °F)

1 730 522

Fuse type

Internal

None

External

Fast blow fuse of 0.5 A

Dielectric strength

1500 V rms, 50 / 60 Hz for 1 min.

Resistance of insulation

>10 MΩ (below 500 VDC)

Sensor voltage: monitoring threshold

OK

> 164 V

Error

< 80 V

Sensor voltage: monitoring response time

on appearance

20 ms < T < 50 ms

on disappearance

5 ms < T < 15 ms

Power consumption 3.3 V

typical

76 mA

maximum

126 mA

Sensor supply consumption

typical

93.60 mA

maximum

154.80 mA

Power dissipation

4.73 W max.