Altitude Operating Conditions

The characteristics in the tables below apply to the modules BMX DDM 16022 and BMX DDM 16022H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.

For detailed information, refer to chapter Operating and Storage Conditions.

General Input Characteristics

The following table shows the general input characteristics of the BMX DDM 16022 and BMX DDM 16022H modules:

Input module type

24 VDC positive logic inputs

Operating temperature

BMX DDM 16022

0...60 ºC (32...140 ºF)

BMX DDM 16022H

-25...70 ºC (-13...158 ºF)

Nominal input values

Voltage

24 VDC

Current

3.5 mA

Threshold input values

At 1

Voltage

≥ 11 V

Current

> 2 mA for U ≥ 11 V

At 0

Voltage

5 V

Current

≤ 1.5 mA

Sensor supply (including ripple)

19...30 V (possibly up to 34 V, limited to 1 hour/day)

Input impedance

At nominal U

6.8 kΩ

Response time

Typical

4ms

Maximum

7ms

Input type

Current sink

Input type in compliance with IEC 61131-2 standard

Type 3

Reverse polarity

Protected

Fuse type

Internal

None

External

1 fast blow fuse of 0.5 A for 8-channel group

2-wire / 3-wire proximity sensor compatibility (IEC 60947-5-2 standard compliant)

2-wire (DC), and 3-wire (DC) PNP any type

Reliability

MTBF for continuous operation in hours at ambient temperature 30 °C (86°F)

427 772

Dielectric strength

Primary/secondary

1500 V actual, 50 / 60 Hz for 1 min.

Between input/output groups

500 VCC

Resistance of insulation

>10 MΩ (below 500 VDC)

Paralleling of inputs

No

Sensor voltage: monitoring threshold

OK

> 18 V

Error

< 14 V

Sensor voltage: monitoring response time at 24 V (-15% ... +20%)

On appearance

8 ms < T < 30 ms

On disappearance

1 ms < T < 3 ms

Power consumption 3.3 V

Typical

79 mA

Maximum

111 mA

24 V pre-actuator consumption

(excluding load current)

Typical

59 mA

Maximum

67 mA

Power dissipation

3.7 W max.

NOTE: These characteristics are available also for the BMX DDM 16022H in the temperature range -25...60 °C (-13...140 °F). At +70 °C (158 °F), the maximum voltage value of input Sensor supply must not exceed 26.4 V.

General Output Characteristics

The following table shows the general output characteristics of the BMX DDM 16022 and BMX DDM 16022H modules:

Output module type

24 VDC positive logic static outputs

Operating temperature

BMX DDM 16022

0...60 ºC (32...140 ºF)

BMX DDM 16022H

-25...70 ºC (-13...158 ºF)

Temperature derating

Apply the temperature derating curve

Nominal values

Voltage

24 VDC

Current

0.5 A

Threshold values

Voltage (including ripple)

19...30 V (34 V possible for 1 hour/day)

Current/channel

0.625 A

Current/module

5 A

Power of tungsten filament lamp

Maximum

6 W

Leakage current

At 0

< 0.5 mA

Voltage drop

At 1

< 1.2 V

Load impedance

Minimum

48 Ω

Response time(1)

1.2 ms

Max. overload time before internal damage

15 ms

Reliability

MTBF for continuous operation in hours at ambient temperature 30 °C (86 °F)

427 772

Frequency of switching to inductive load

0.5 / LI2 Hz

Paralleling of outputs

Yes (maximum of 2)

Compatibility with IEC 61131-2 DC direct inputs

Yes (type 3 and no type)

Built-in protection

Against over voltage

Yes, by Transil diode

Against inversions

Yes, by inverted diode(2)

Against short-circuits and overloads

Yes, by current limiter and electric circuit-breaker 1.5 In < Id < 2 In

Fuse type

Internal

None

External

1 fast blow fuse of 6.3 A for 8-channel group

Pre-actuator voltage: monitoring threshold

OK

> 18 V

Error

< 14 V

Pre-actuator voltage: monitoring response time at 24 V (-15% ... +20%)

On appearance

8 ms < T < 30 ms

On disappearance

1 ms < T < 3 ms

Power consumption 3.3 V

Typical

79 mA

Maximum

111 mA

24 V pre-actuator consumption

(excluding load current)

Typical

59 mA

Maximum

67 mA

Power dissipation

3.7 W max.

Dielectric strength

Output / ground or output / internal logic

1500 V actual, 50 / 60 Hz for 1 min.

Resistance of insulation

>10 MΩ (below 500 VDC)

(1) All outputs are equipped with fast demagnetization circuits for electromagnets. Electromagnet discharge time < L/R.

(2) Provide a 6.3 A fuse to the +24 V pre-actuator supply

NOTE: The characteristics in this table also apply to the BMX DDM 16022H in the temperature range -25...60 °C (-13...140 °F).

At 70 °C (140 °F):

  • The maximum voltage of the pre-actuator power supply must not exceed 26.4 V.

  • The maximum output current must not exceed 0.55 A.