At a Glance
The general characteristics of the removable ABS-7E•• static input relays for TELEFAST 2 bases are described in this section.
General Characteristics
This table shows the general characteristics of the ABS-7E•• relays.
ABS-7E•• reference |
C3AL |
C3B2 |
C3E2 |
A3E5 |
A3F5 |
A3M5 |
|
---|---|---|---|---|---|---|---|
Relay width |
12.5 mm |
||||||
Command characteristics |
|||||||
Assigned operating voltage (Us) |
Direct |
5 V |
24 V |
48 V |
- |
||
Alternating |
- |
48 V |
110..130 V |
230..240 V |
|||
Max. operating voltage (including ripple) |
6 V |
30 V |
60 V |
53 V |
143 V |
264 V |
|
Max. current at Us |
13.6 mA |
15 mA |
12 mA |
8.3 mA |
8 mA |
||
State 1 guaranteed |
Voltage |
3.75 V |
11 V |
30 V |
32 V |
79 V |
164 V |
Current |
4.5 mA |
6 mA |
5 mA |
4.5 mA |
|||
State 0 guaranteed |
Voltage |
2 V |
5 V |
10 V |
30 V |
40 V |
|
Current |
0.09 mA |
2 mA |
1.5 mA |
2 mA |
|||
Maximum switching frequency (cyclic report 50%) |
1000 Hz |
25 Hz |
|||||
Complies with IEC1131-2 |
- |
Type 2 |
Type 1 |
||||
Response time |
State 0 to 1 |
0.05 ms |
20 ms |
||||
State 1 to 0 |
0.4 ms |
20 ms |
|||||
Voltage assigned to insulation |
Input/output |
300 V |
|||||
Voltage assigned to shock resistance (1.2/50) |
Input/output |
2.5 kV |