At a Glance

The general characteristics of the removable ABS-7S•• static output relays for TELEFAST 2 bases are described in this section.

General Characteristics

This table shows the general characteristics of the ABS-7S•• relays.

ABS-7S•• reference

C2E

A2M

C3BA

C3E

A3M

Relay width

10 mm

12.5 mm

Output circuit characteristics

Voltage assigned to job

Direct

5..48 V

-

24 V

5..48 V

-

Alternating

-

24..240 V

-

24..240 V

Max. voltage

57.6 VDC

264 VAC

30 VDC

60 VDC

264 VAC

Alternating current load

Resistive, load AC12

Current

-

0.5 A

-

2 A

Direct current load

Resistive, load DC12

Current

0.5 A

-

2 A

1.5 A

-

Inductive load DC13

Current

-

-

0.3 A

-

Filament lamp load DC6

-

10 W

-

Leakage current at state 0

<= 0.5 mA

<= 2 mA

<= 0.3 mA

<= 2 mA

Breakdown voltage at state 1

<= 1 V

<= 1.1 V

<= 0.3 V

<= 1.3 V

Minimum current through channel

1 mA

10 mA

1 mA

10 mA

Response time

State 0 to 1

0.1 ms

10 ms

0.1 ms

10 ms

State 1 to 0

0.6 ms

10 ms

0.02 ms

0.6 ms

10 ms

Switching frequency on inductive load

-

< 0.5 LI2

-

Voltage assigned to insulation

Input/output

300 V

Voltage assigned to shock resistance (1.2/50)

Input/output

2.5 kV