Altitude Operating Conditions

The characteristics in the table below apply to the modules BMX DDI 3232 and BMX DDI 3232H for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.

For detailed information, refer to chapter Operating and Storage Conditions.

General Characteristics

This table presents the general characteristics for the BMX DDI 3232 and BMX DDI 3232H modules.

Module type

12 VDC/24 VDC positive or negative

logic inputs

Operating temperature

BMX DDI 3232

0...60 ºC (32...140 ºF)

BMX DDI 3232H

-25...70 ºC (-13...158 ºF)

Nominal input values

Voltage

12 VDC/24 VDC

Current

3.3 mA

Threshold input values

At 1

Voltage

≥ 10 V (sink) or ≤ –10 V (source)

Current

≥ 2 mA

At 0

Voltage

≤ 5 V (sink) or ≥ -5 V (source)

Current

≤ 1.5 mA

Sensor supply (including ripple for standard module)

19...30 V

Input impedance

At nominal U

7.27 kΩ

Response time

Typical

4 ms

Maximum

7 ms

Reliability

MTBF in hours at ambient temperature 30 °C (86 °F)

700 785

Reverse polarity

Protected

Fuse type

Internal

None

External

1 fast blow fuse of 0.5 A

Input type

Current sink/source

IEC 61131-2 compliance (24 VDC input)

Type 3

IEC 61131-2 compliance (12 VDC input)

2-wire / 3-wire proximity sensor compatibility (IEC 60947-5-2 standard compliant)

2-wire (DC), and 3-wire (DC)

Dielectric strength

Primary/Secondary

1500 V actual, 50 / 60 Hz for 1 min.

Between channel groups

1500 V actual, 50 / 60 Hz for 1 min.

Resistance of insulation

>10 MΩ (below 500 VDC)

Paralleling of inputs(1)

Yes

Sensor voltage: monitoring threshold

OK

> 19VDC

Error

< 14 VDC

Sensor voltage: monitoring response time at 24 V (-15% ... +20%)

On appearance

1 ms < T < 3 ms

On disappearance

8 ms < T < 30 ms

Power consumption 3.3 V

Typical

100 mA

Maximum

130 mA

Power consumption 24 V

Typical

7.6mA

Maximum

11.5 mA

Sensor supply consumption(2)

Typical

110 mA

Maximum

125 mA

Power dissipation

4.7 W max.

Temperature derating for BMX DDI 3203

None

(1) This characteristic is used to connect several inputs to the same module in parallel or to different modules for input redundancy.

NOTE: The power monitoring is effective only when the group input shares the same power supply. The module is able to customize sink/source by channel in case the power supply monitor function is disabled. Refer to the topic for additional information about usage of the power monitoring function and power supply connections.