How to adjust the speed measurement and monitoring function
(Original Document)
At a Glance
This parametering is offered with the TSX CTY 2C module.
The Speed monitoring zone is used to define:
Procedure
The table below summarizes the procedure for adjusting the speed measurement and monitoring function.
Step
Action
1
Open the module to be set.
2
In the channel field, select or enable the counter selection (i.e. the channel) involved.
3
In the general parameters field, select or enable the counting function.
4
Access the adjustment screen by clicking on the Adjustment tab.
5
In the Speed monitoring zone enter the required overspeed threshold value.
This value must be between: 1 and 4 000 000 pulses/s.
The value 0 inhibits the overspeed monitoring.
6
Enter the value of the measurement period, according to the estimated pulse frequency and the desired precision or response time.
This value must be between: 10 and 30 000 ms.
7
Speed reading function and monitoring adjustment is complete.
  • If there are no more parameters to be defined, enable the new adjustment with the Edit → Enable command.
Note: in offline mode, the value entered is then copied again in the Initial value field. In on-line mode, the value entered then becomes the current value.