How to adjust threshold and set point values
(Original Document)
At a Glance
These parameters define threshold values 0 and 1 and high and low setpoints.
These objects have very similar roles in comparisons.
Parameters are set in the Threshold value and Setpoint value zones in the adjustment screen.
Procedure
The table below summarizes the procedure for adjusting threshold values.
Step
Action
1
Open the module to be set.
2
In the channel field, select or enable the counter selection (i.e. the channel) involved.
3
In the general parameters field, select or enable the counting function.
4
Access the adjustment screen by clicking on the Adjustment tab.
5
In the Threshold value zone enter the required values.
These values must be between:
  • -16 777 216 and +16 777 215 in normal mode,
  • 0 and the rollover value if this mode is configured or implicit (TSX CTY 2C, absolute encoder interface).
Note: the respective values of threshold 0 and threshold 1 do not have to be in this order.
6
In the Set point value zone enter the value(s) required; when they are defined (depending on the module and the counting function configured).
These values must be between: -16 777 216 and +16 777 215.
7
Threshold and set point value adjustment is complete.
  • If there are no more parameters to be defined, enable the new adjustment with the Edit → Enable command.
Note: in offline mode the value entered is then copied in the Initial value fields. In on-line mode the values entered then become the current values.