Step
|
Action
|
---|---|
1
|
Export your application out of your legacy programming system (e.g. as an FEF file out of PL7).
|
2
|
Create a new application in Control Expert selecting a CPU with enough memory and the I/O access capabilities needed (e.g. Modicon M340).
Optionally you can configure the I/O modules expected to be needed but you can modify the hardware configuration even later (see step 6).
|
3
|
Launch the conversion wizard in Control Expert via Tools → Convert Partially.
Result: The conversion wizard asks you to select the exported legacy source file.
|
4
|
Select the exported legacy source file.
Result: The converter analyzes the source file and displays the result in the 3 tabs of the conversion wizard.
|
5
|
Select the parts of the application (or the complete application) to be converted in the Structure tab.
|
6
|
Remap the I/O objects for getting them compliant with the new hardware configuration.
Concurrently you can modify the hardware configuration of the new application in Control Expert.
Note: To save a backup file of your intermediate I/O mapping you can use the Save button. With Load you can reload your latest saved intermediate I/O mapping.
|
7
|
After finishing all your selections and manual modifications click OK.
Result: The converter applies the defined remapping to the selected parts of the source file and imports the results into the opened Control Expert Application (e.g. an application with a Modicon M340 PLC).
|
8
|
Continue working on the opened application, save it or export as an XEF file.
|