Processors Supporting the TSX CPP 110 Card
(Original Document)
At a Glance
All Premium and Atrium processors support the CANopen PCMCIA card.
The card is implemented using Control Expert software.
The general configuration of a CANopen bus is defined using the Sycon software, version 2.8 or higher (TLX LFBCM).
NOTE: It is mandatory for the PCMCIA card to be installed in the slot located in the processor module. As a result, only one CANopen bus is available for each PLC CPU.
Types of Processors and Capacities
The following table gives details of the processors supporting the TSX CPP 110 CANopen PCMCIA card, and their maximum storage capacities.
Processor
Maximum size of TSX CPP 110 configuration data located in the processor(1)
Maximum size of input/output data for the CANopen node configuration
MAST task
FAST task
TSX P57 0••
TSX P57 1••
TSX P57 1•••
12 Kb
384 %MW
(192+192)
48 %MW
(24+24)
TSX P57 2••
TSX P57 2•••
TSX PCI 57 204
16 Kb
512 %MW
(256+256)
64 %MW
(32+32)
TSX P57 3••
TSX P57 3•••
TSX PCI 57 354
32 Kb
1024 %MW
(512+512)
128 %MW
(64+64)
TSX P57 4••
TSX P57 4•••
TSX P57 5••
TSX P57 5•••
TSX P57 6•••
64 Kb
3584 %MW
(1792+1792)
512 %MW (2)
(256+256)
Key
(1): This maximum size can be exceeded if you load the configuration into the card using the Sycon software. The maximum size of configuration data authorized by the Sycon software is 64 Kb.
(2): The maximum size of input/output data for the CANopen node configuration (FAST task) is 1024 %MW (512+512) for TSX P57 554, TSX P57 5634 and TSX P57 6634 with V3.0 firmware version.
NOTE: The configuration fill rate is given in the word %KWm.1.2.